ULTRASONIC
6
Copyright STULZ GmbH 02/1997
Humidifier Path
The length of the humidifier path is dependent on different factors.
- even distribution of the mist in the airflow
- air temperature
- relative air humidity
- air speed
The following diagram for the determation of the humidifier path contains standard
values dependent on the most important parameters. (Air temperature 18°C to
24°C). The tolerance is approx. ± 0.5 m.
If no place is available for the humidifier path, use of a mist collector is possible. The
smaller the distance to the mist collector, the larger the loss effect of the humidifier
and the more water is drained off into the pan, which has to be drained off for
hygienic reasons. Another possibility to reduce the humidifier path is the employ-
ment of a proportional control. With this control, the output of the humidifiers is
reduced dependent on the requirements in more than 90% of the operating time
and therefore reduces the humidifier path, saves the oscillators and maintains an
even distribution of the mist even in operation under partial load.
TECHNICAL DATA ENS SERIES
2.1