ULTRASONIC
41
Copyright STULZ GmbH 02/1997
ASSEMBLY ENS SERIES
Water Supply Lines
1) Only use fully demineralized water <5µS/cm together with the humidifier.
Install one check valve in each humidifier. Admission pressure 0.5 to 5 bar.
2) Perform connection between demineralization unit and the humidifier by
means of a material that is resistant to fully demineralized water (e.g. PE or
stainless steel (1.4571).
3) Swarf and dirt accumulation must not get into the water lines. Clean all lines
before connecting them to the humidifier. Dependent on the safety risk, either
use pressure tubing or stainless steel pipe to make the water lines.
4) Install the safety overflow. Under standard operating conditions, no water will
flow out of the overflow pipe.
Hydraulic Schematic Diagram