Terminal Configuration
Terminal 1
+0.... 10 V DC
reverse battery protected con-
Terminal 2
GND
troller input R
in
=20 kOhm
Terminal 3
+0....20 V DC
reverse battery protected con-
Terminal 4
GND
troller input R
in
=40 kOhm
Terminal 5
+0....20 mA DC
reverse battery protected con-
Terminal 6
GND
troller input R
in
=1 kOhm
Terminal 7
0.....20 (30) V AC
isolated controller input
Terminal 8
GND
R
in
>150 kOhm,
via TP1*
adjustable to 20/30 V
Terminal 9
Bath response
humidifier response
Terminal10
Bath response
release by water level
48VAC/50Hz
Terminal 11
Supply voltage
12 V AC supply voltage
Terminal 12
Supply voltage
of P-adapter ~1W
Terminal 13
Input 48 VAC
no voltage relay contract
Terminal 14
Output
for water intake valve
Terminal A1
Input 48 VAC
No voltage electronic no
Terminal A2
Output
voltage a.c. zero voltage switch
load 24...280 V AC/50 Hz
21 A steady load
40 A short-time load
*
Adjustment TP 1
Left-hand stop:
0......30 V
Right-hand stop:
0......20 V
TP1
Power
elektronics
Terminals
FUNCTION OF PROPORTIONAL ADAPTER
}
}
}
}
}
}
}
}