E/0618/35A/68
Start time
Current limit start setting ( when selected)
DIP switch number
DIP switch number
1
2
Time [S] 4
5
Current limit % FLA
OFF
OFF
2
OFF
OFF
150 %
ON
OFF
5
ON
OFF
250 %
OFF
ON
10
OFF
ON
350 %
ON
ON
15
ON
ON
450 %
Start time (current limit or soft start) Soft start initial torque setting (when selected)
DIP switch number
DIP switch number
3
4
5
Initial torque % LRT
OFF
Current limit
OFF
OFF
15 %
ON
Soft start
ON
OFF
25 %
OFF
ON
35 %
ON
ON
65 %
Overload class selection
DIP switch number
11
12
Trip class
OFF
OFF
OFF
ON
OFF
10
OFF
ON
15
ON
ON
20
Overload reset
Auxiliary relay #1
DIP switch number
DIP switch number
13
Reset
14
Setting
OFF
Curren limit OFF
Normal
ON
Soft start
ON
Up-to-speed
Содержание Tel-Air-2 Series
Страница 2: ......
Страница 18: ...E 0618 35A 18 Air flow diagram TLU units a unit size 2 is shown in these drawings COOLING FREE COOLING...
Страница 27: ...E 0618 35A 27 TLD F 40 TLD F 60 TLD F 80 TLD F 40 TLD F 80...
Страница 28: ...E 0618 35A 28 TLD F 90 TLD F A2 TLD F A4 TLD F 90 TLD F A4...
Страница 29: ...E 0618 35A 29...
Страница 30: ...E 0618 35A 30...
Страница 31: ...E 0618 35A 31...
Страница 37: ...E 0618 35A 37 Cut out TLF TLD 40 60 EXTERNAL OUTSIDE...
Страница 38: ...E 0618 35A 38 Cut out FLOOR TLD 40 60 FRONT SIDE REAR SIDE...
Страница 39: ...E 0618 35A 39 Cut out TLU 40 60 EXTERNAL OUTSIDE...
Страница 40: ...E 0618 35A 40 Cut out TLF TLD 80 A4 EXTERNAL OUTSIDE...
Страница 41: ...E 0618 35A 41 Cut out FLOOR TLD 80 A4 FRONT SIDE REAR SIDE...
Страница 42: ...E 0618 35A 42 Cut out TLU 80 A4 EXTERNAL OUTSIDE...
Страница 61: ...E 0618 35A 61...
Страница 62: ...E 0618 35A 62...
Страница 63: ...E 0618 35A 63...
Страница 64: ...E 0618 35A 64...
Страница 72: ......