Maintenance
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A-
11.4. Cleaning
11.4.1. Cleaning water-bearing parts
If checks reveal that the above parts feature bacteria or mineral salts, clean the unit as follows:
3
If microbial contamination is present:
a) Brush or spray all parts with 5 %
hydrogen peroxide solution (H
2
O
2
) a
minimum of three times at 15-minute
intervals.
b) After an exposure time of approx. 30
min, rinse parts thoroughly several
times with water.
c) Flush water pipes with the highest
possible pressure before connecting
units to the water mains.
2
Remove mineral salt residues using
commercially available cleaning agents.
We recommend gentle, odorless deter
-
gents based on citric acid
1
Thoroughly clean all water-bearing parts
with water and a cloth or brush, using
demineralized drinking water.
Slacken but do not fully remove the screws.
CAUTION
Danger of death. Electric shock risk.
Switch off power to the system before cleaning!
WARNING
DANGER
CAUTION
Hard objects.
Do not use hard objects!
IMPORTANT
CAUTION
Microbial contamination.
If microbial contamination is evident, also inspect
the water treatment system for this contamination.
CAUTION
Ventilation.
Ensure adequate ventilation.
CAUTION
Risk of chemical burns.
Use safety goggles when handling cleaning
agents or hydrogen peroxide solution. These
compounds are "caustic"!