Series GEN 2 Ultrasonic Humidifier IOM Manual
Operation
Purge the Water Line
Before operating the unit, metal shavings or debris that may form during the installation process must be
flushed from the
water supply piping. Take these steps before allowing water to
fl
ow into the Ultrasonic
Humidifier:
1.
Verify the main disconnect switch from the control box is set to Off.
2.
With the water supply valve closed, disconnect the supply tubing from the
filter strainer
in the
back of the unit.
3.
Open the supply valve and
fl
ush the tubing into a bucket or building drain for about 30 seconds.
4.
After the water line is purged, close the valve and reconnect the supply line to the inlet strainer and
fl
ow regulator.
Initial Operation Checklist
For new installations, prior to start up, ensure the unit is ready to operate by verifying the following
checklist.
The humidifier is installed horizontally and
level.
No obstacle is in front of the atomizing direction.
The electrical wiring is correctly connected.
Power to the humidifier is
48VDC.
DI or RO supply water is used.
The water supply piping and drain piping are correctly connected and secured.
All parts are correctly installed.
After the above items are verified
, the humidifier is ready to operate.
Operation Procedure
1.
Turn on power.
2.
Verify the fan is operating.
3.
Turn the main power source switch on the control box to the On position.
4.
Open the water supply valve.
This allows
water to flow to the
humidifier.
5.
Perform a manual drain cycle to flush any particulates from the tank u
sing the system
controller (see STULZ Ultra-Series Controller IOM Manual OUU0078).
6.
Set the humidity setpoint to the desired humidity level.
Water is supplied to the water tank and when the required water level is reached, the ultrasonic
nebulizers will start producing atomized mist.
7.
If the
humidifier
does not start, increase the setpoint of the humidistat.
Mist is carried through mist guide by the
fl
ow of air from the
AHU’s fan.
The mist is delivered
through the ductwork thus humidifying the surrounding air.
The
humidifier
starts and stops by means of a signal from the control box.
8.
During operation, the water level in the tank is maintained by the level controller.
9.
If the water level in the tank falls below the safety level for any reason during operation,
power to the ultrasonic humidifier nebulizers is cut off by the level controller.
After operation starts, verify the following items on a regular basis:
Содержание DAH
Страница 37: ...Series GEN 2 Ultrasonic Humidifier IOM Manual DAH 04 16 Typical Wiring Diagram for Modbus Version 26 ...
Страница 38: ...Series GEN 2 Ultrasonic Humidifier IOM Manual DAH 04 16 Typical Wiring Diagram for Stand Alone Version ...
Страница 39: ...Series GEN 2 Ultrasonic Humidifier IOM Manual DAH 24 30 Typical Wiring Diagram for Stand Alone Version 28 ...
Страница 40: ...Series GEN 2 Ultrasonic Humidifier IOM Manual DAH 24 30 Typical Wiring Diagram for Stand Alone Version ...
Страница 41: ...Series GEN 2 Ultrasonic ...