Stulz CyberRow DX CRS-042-AR Скачать руководство пользователя страница 8

8

 QEWR002G   ©STULZ USA – All rights reserved

CYBERROW DX ENGINEERING MANUAL

CRS-( )-

AR 

TE

CHNIC

AL

 D

A

T

A

DX SYSTEM

CRS-042

CRS-084

CRS-090

-AR

-AR

-AR

Blower/Motor - Backward Inclined, Plenum Style Fan, with an EC Motor

Horsepower (Each)

1/4 H.P. 

1/4 H.P.

1/4 H.P.

CFM

1,500

2,900

2,900

Quantity of Blowers 

3

3

3

Drive Method

Direct 

Direct

Direct

Direct Expansion (DX) Coil

Evaporator Coil  -  Aluminum Fin, Copper Tube

Rows/Face Area (ft

2

)

3/5.8

4/5.8

4/5.8

Face Velocity, fpm

260

500

500

Compressor  -  Heat pump duty rated Scroll - R410A

Type, (Qty.)

Scroll (1) 

Scroll (1)

Scroll (1)

Watts Input

3,680

7,090

7,830

Tot. Heat of Rej. (MBH)

64.6

124

131.8

Condenser Type

Remote Air Cooled

Head Pressure Control

See Remote Condenser Selection

Connection Sizes  -  Copper

Condensate Drain, (w/ pump)

1/2” FPT 

1/2” FPT

1/2” FPT

Hot Gas & Liquid Refrigerant 

Connections (Air Cooled)

5/8" O.D.

5/8" O.D.

5/8" O.D.

Physical Data

Approx. Weight (lbs)

450

480

480

Dimensions:  (H”xW”xD”) 

(without side diverter panel option)

77.8" x 11.6" x 42.1"

Approx. Shipping Weight (lbs)

636

665

665

Approx.Shipping Dimensions 

(H”xW”xD”)

84" x 22" x 48" 

Содержание CyberRow DX CRS-042-AR

Страница 1: ...1 STULZ USA All rights reserved QEWR002G CYBERROW DX ENGINEERING MANUAL CyberRow DX Row Based Precision Air Handling Units 12kW 33kW 60 Hz DX Air Water Glycol Floor Mounted Systems Engineering Manual...

Страница 2: ...tions GLOBAL LEADER From our beginnings in Germany 70 years ago to our expansionthroughouttheworld STULZisalwaysinnovating Today STULZ has seven global production plants and hundreds of sales and serv...

Страница 3: ...ING MANUAL Table of Contents Model Nomenclature 4 Model Features 4 Model Nomenclature Speci cations 5 Con gurations 6 Product Features 7 Technical Data 8 10 Electrical Data 11 Sound Data 11 Dimensiona...

Страница 4: ...ustry 12 and 24 cabinet widths 3 EC Fans Independently and in nitely adjustable EC fans ensure maximum ef ciency Used in containment open architecture and hot spot reduction applications Adapts to bot...

Страница 5: ...nstalled head pressure waterregulating controlvalve s Condenser source water shall be provided by a cooling tower or some other remote water source Head Pressure Control Head pressure shall be automat...

Страница 6: ...om IT equipment and prevents from mixing with cool air The front of IT equipment is accessed in the external cold aisle The STULZ CyberRow draws the contained hot air from the hot aisle removes the he...

Страница 7: ...dard Dual Power Connection N A N A N A Remote Stop Start Contacts Standard Standard Standard Main Power Switch Standard Standard Standard E MICROPROCESSOR CONTROLLER A C Grouping pLAN Interface Option...

Страница 8: ...8 4 5 8 Face Velocity fpm 260 500 500 Compressor Heat pump duty rated Scroll R410A Type Qty Scroll 1 Scroll 1 Scroll 1 Watts Input 3 680 7 090 7 830 Tot Heat of Rej MBH 64 6 124 131 8 Condenser Type R...

Страница 9: ...ing 2 Way Water Valve Optional Control Modulating 3 Way Water Valve Compressor Heat pump duty rated Scroll R410A Type Qty Watts Input 2 820 3 940 5 690 7 470 6 290 8 250 Tot Heat of Rej MBH 66 64 128...

Страница 10: ...92 98 106 96 Total KW 14 3 15 4 14 0 27 4 29 7 26 8 29 31 28 Sensible 14 3 15 4 14 0 27 4 29 7 26 8 29 31 28 90 FDB 66 1 FWB Entering Air Temperature Total MBH 46 50 45 88 97 88 93 102 91 Sensible 46...

Страница 11: ...614 speci es a method for measuring the component of sound intensity that is normal to a measurement surface The measurement surface is chosen to enclose the noise source s so that the sound power lev...

Страница 12: ...PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION 11 6 77 8 42 1 CONDENSATE CONNECTION PIPING CONNECTION POWER CONNECTION AIROUT AIRIN AIR OUT AIR OUT AIR IN AIR IN POWER POWE...

Страница 13: ...tandards of quality management to ensure product quality Each system shall be subjected to a complete operational and functional test procedure at the factory prior to shipment CABINET Side access pan...

Страница 14: ...Flooded Control AR The air cooled system shall incorporate a low ambient ooded head pressure control The pressure control shall be for year REFRIGERATION SYSTEM All piping and components contained wi...

Страница 15: ...ach high voltage circuit shall be individually protected by circuit breakers or manual motor starters on all three phases The blower motor shall have thermal and short circuit protection Line voltage...

Страница 16: ...creens PASSWORD PROTECTION Access to the Info Menu Alarms Log and the ability to monitor room conditions shall be allowed without the use of a password Modi cations to the control setpoints shall requ...

Страница 17: ...20 ft long remote strip cable type water and leak detector shall be provided for remote eld installation Upon sensing a water leak the normallyclosedwaterdetectorcontrol circuit shall open thereby sh...

Страница 18: ...18 QEWR002G STULZ USA All rights reserved CYBERROW DX ENGINEERING MANUAL NOTES...

Страница 19: ...19 STULZ USA All rights reserved QEWR002G CYBERROW DX ENGINEERING MANUAL NOTES...

Страница 20: ...28918 Legan s Madrid STULZ France S A R L 107 Chemin de Ronde 78290 Croissy sur Seine info stulz fr STULZ S p A Via Torricelli 3 37067 Valeggio sul Mincio VR STULZ CHSPL India Pvt Ltd 006 Jagruti Ind...

Отзывы: