modulation of the unit’s cooling capacity, and evaporator coil 
freeze protection under low load conditions.   

PIPING CONFIGURATION 

Top Piping:

 When top piping is specifi ed, the CyberRow units 

shall be provided with connections for water/glycol or refrigerant 
piping and condensate discharge on the top of the cabinet.

Bottom Piping:

 When bottom piping is specifi ed (e.g. raised 

fl oor applications), the CyberRow units shall be provided 
with connections for water/glycol or refrigerant piping and 
condensate pump discharge through the bottom of the cabinet.

CONDENSATE PUMP

The CyberRow shall include a factory wired and installed 
condensate pump. The condensate pump shall have the capacity 
of 80 gal/hr. at 23 ft. of lift with a maximum shut off (head) of 
115 ft. The condensate pump shall be piped with either top or 
bottom discharge connections, to remain consistent with top or 
bottom piping connections.

RETURN AIR SENSOR

A factory mounted and wired temperature sensor (NTC) mounted 
in the return air stream temperatures shall be provided.

SUPPLY AIR CONTROL (OPTIONAL)

The STULZ CyberRow shall be provided with a temperature and 

humidity sensor factory unit mounted in the return air stream and 
a fi eld installed supply air temperature (optional) and humidity 
sensor for supply air temp control capabilities. The controller 
shall provide the user an adjustable supply air control setpoint. 

AIR COOLED HEAT REJECTION

-20°F Variable Fan Speed Control (AR)

The air cooled system shall incorporate a low ambient, variable 
speed fan, head pressure control. The pressure control shall be 
for year-round air conditioning system operation down to -20°F 
DB minimum ambient air temperature.

-30°F Flooded Control (AR)

The air cooled system shall incorporate a low ambient, fl ooded 
head, pressure control. The pressure control shall be for year-

REFRIGERATION SYSTEM

All piping and components contained within the 
refrigeration system shall be rated for use with R410A 
refrigerant. Each refrigeration circuit shall include, as 
a minimum a refrigerant drier/strainer, sight glass with 
moisture detector, an electronic thermal expansion 
valve, an evaporator coil, a compressor, a high pressure 
switch with manual reset, and a low pressure switch with 
automatic reset.

FIXED SPEED SCROLL COMPRESSOR

The compressor shall be a high effi ciency, high reliability 
and low noise scroll compressor.

The compressor shall be equipped with internal line 
break motor protectors, an internal pressure relief valve 
and external vibration mounting isolation.

VARIABLE SPEED COMPRESSOR 
(CRS-090)

The speed of the compressor shall be controlled with 
a variable frequency drive (VFD) to match compressor 
capacity to the actual thermal load. The VFD shall be 
capable of providing power for the compressor to operate 
up to 120rpm. The VFD shall proportionally control the 
compressor motor speed to maintain a constant supply 
air temperature.

EVAPORATOR COIL

The evaporator coil shall be constructed of seamless 
drawn copper tubes, mechanically bonded to tempered 
aluminum fi ns (that have an enhanced design for 
maximum heat transfer), and mounted in a stainless steel 
condensate drain pan. The coil shall be designed for a 
maximum of 500 ft./min. face velocity.

PROPORTIONAL ELECTRONIC 
EXPANSION VALVE

An electronically operated thermostatic expansion valve 
shall be installed to precisely control the fl ow of liquid 
refrigerant into the evaporator coil while maintaining 
the desired superheat across a wide range of operating 
conditions. 

 

ELECTRONIC HOT GAS BYPASS
(CRS-042/084)

An electronically operated hot gas bypass valve shall 
be installed. The hot gas bypass valve shall provide 

Содержание CyberRow DX CRS-042-AR

Страница 1: ...1 STULZ USA All rights reserved QEWR002G CYBERROW DX ENGINEERING MANUAL CyberRow DX Row Based Precision Air Handling Units 12kW 33kW 60 Hz DX Air Water Glycol Floor Mounted Systems Engineering Manual...

Страница 2: ...tions GLOBAL LEADER From our beginnings in Germany 70 years ago to our expansionthroughouttheworld STULZisalwaysinnovating Today STULZ has seven global production plants and hundreds of sales and serv...

Страница 3: ...ING MANUAL Table of Contents Model Nomenclature 4 Model Features 4 Model Nomenclature Speci cations 5 Con gurations 6 Product Features 7 Technical Data 8 10 Electrical Data 11 Sound Data 11 Dimensiona...

Страница 4: ...ustry 12 and 24 cabinet widths 3 EC Fans Independently and in nitely adjustable EC fans ensure maximum ef ciency Used in containment open architecture and hot spot reduction applications Adapts to bot...

Страница 5: ...nstalled head pressure waterregulating controlvalve s Condenser source water shall be provided by a cooling tower or some other remote water source Head Pressure Control Head pressure shall be automat...

Страница 6: ...om IT equipment and prevents from mixing with cool air The front of IT equipment is accessed in the external cold aisle The STULZ CyberRow draws the contained hot air from the hot aisle removes the he...

Страница 7: ...dard Dual Power Connection N A N A N A Remote Stop Start Contacts Standard Standard Standard Main Power Switch Standard Standard Standard E MICROPROCESSOR CONTROLLER A C Grouping pLAN Interface Option...

Страница 8: ...8 4 5 8 Face Velocity fpm 260 500 500 Compressor Heat pump duty rated Scroll R410A Type Qty Scroll 1 Scroll 1 Scroll 1 Watts Input 3 680 7 090 7 830 Tot Heat of Rej MBH 64 6 124 131 8 Condenser Type R...

Страница 9: ...ing 2 Way Water Valve Optional Control Modulating 3 Way Water Valve Compressor Heat pump duty rated Scroll R410A Type Qty Watts Input 2 820 3 940 5 690 7 470 6 290 8 250 Tot Heat of Rej MBH 66 64 128...

Страница 10: ...92 98 106 96 Total KW 14 3 15 4 14 0 27 4 29 7 26 8 29 31 28 Sensible 14 3 15 4 14 0 27 4 29 7 26 8 29 31 28 90 FDB 66 1 FWB Entering Air Temperature Total MBH 46 50 45 88 97 88 93 102 91 Sensible 46...

Страница 11: ...614 speci es a method for measuring the component of sound intensity that is normal to a measurement surface The measurement surface is chosen to enclose the noise source s so that the sound power lev...

Страница 12: ...PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION 11 6 77 8 42 1 CONDENSATE CONNECTION PIPING CONNECTION POWER CONNECTION AIROUT AIRIN AIR OUT AIR OUT AIR IN AIR IN POWER POWE...

Страница 13: ...tandards of quality management to ensure product quality Each system shall be subjected to a complete operational and functional test procedure at the factory prior to shipment CABINET Side access pan...

Страница 14: ...Flooded Control AR The air cooled system shall incorporate a low ambient ooded head pressure control The pressure control shall be for year REFRIGERATION SYSTEM All piping and components contained wi...

Страница 15: ...ach high voltage circuit shall be individually protected by circuit breakers or manual motor starters on all three phases The blower motor shall have thermal and short circuit protection Line voltage...

Страница 16: ...creens PASSWORD PROTECTION Access to the Info Menu Alarms Log and the ability to monitor room conditions shall be allowed without the use of a password Modi cations to the control setpoints shall requ...

Страница 17: ...20 ft long remote strip cable type water and leak detector shall be provided for remote eld installation Upon sensing a water leak the normallyclosedwaterdetectorcontrol circuit shall open thereby sh...

Страница 18: ...18 QEWR002G STULZ USA All rights reserved CYBERROW DX ENGINEERING MANUAL NOTES...

Страница 19: ...19 STULZ USA All rights reserved QEWR002G CYBERROW DX ENGINEERING MANUAL NOTES...

Страница 20: ...28918 Legan s Madrid STULZ France S A R L 107 Chemin de Ronde 78290 Croissy sur Seine info stulz fr STULZ S p A Via Torricelli 3 37067 Valeggio sul Mincio VR STULZ CHSPL India Pvt Ltd 006 Jagruti Ind...

Отзывы: