CYBERROW DX ENGINEERING MANUAL

PRODUCT

 GUIDE SPE

CIFIC

A

TIONS

round system operation down to -30°F DB minimum ambient air 
temperature. Liquid refrigerant receivers, with receiver liquid-
level sight glass and head pressure regulator valves (for fl ooded 
condenser operation) shall be included, but not factory installed.

WATER/GLYCOL COOLED HEAT 

REJECTION

Stainless Steel Brazed-Plated (W/G)

The evaporator refrigerant circuit shall be provided with a factory 
installed single pass, counterfl ow  confi gured, brazed plate heat 
exchanger, with integral subcooler. It shall be constructed of type 
316 stainless steel; designed and tested for a 650 psig. w.w.p.

2-Way, 600 psig Regulating Valve (W/G)
(Standard)

The refrigerant circuit head pressure shall be controlled by a 
factory installed 2-way water/glycol regulating valve rated for 400 
psig. w.w.p. The 2-way condenser water modulating valve shall 
automatically meter the fl ow of water to the condenser. It shall do so, 
in response to a proportional signal (0-10VDC) provided to the valve 
by the microprocessor controller.

3-Way, 600 psig Regulating Valve (W/G)
(Optional)

The refrigerant circuit head pressure shall be controlled by a 
factory installed 3-way water/glycol regulating valve rated for 400 
psig w.w.p. The 3-way condenser water modulating valve shall 
automatically meter the fl ow of water/glycol to the condenser. It 
shall do so, in response to a proportional signal (0-10VDC) provided 
to the valve by the microprocessor controller.

ELECTRICAL SYSTEM

The electrical system shall conform to National Electrical Code 
(NEC) requirements. In accordance with NEC Class II requirements, 
the control circuit shall be 24 volts AC wire, and shall not be smaller 
than 18 AWG. All wiring shall be neatly wrapped on run in conduit, or 
cable trays, and routed in bundles. Each wire shall end with a service 
loop and be securely fastened by an approved method. Each wire in 
the unit shall be numbered for ease of service tracing. 

All electrically actuated components shall be easily accessible from 
the front of the unit without reaching over exposed high voltage 
components or rotating parts. Each high voltage circuit shall be 
individually protected by circuit breakers, or manual motor starters, 
on all three phases. The blower motor shall have thermal and short 

circuit protection. Line voltage and 24 volt control circuit 
wiring shall be routed in separate bundles. The electric 
box shall include all the contactors, starters, fuses, circuit 
breakers, terminal boards, and transformers required for 
operation of the CyberRow unit. It shall also allow for full 
service via front and rear access panels.

 

REMOTE STOP/START CONTACTS

Included in the system’s electrical control circuit shall be 
a 2-pin terminal connection for remote stop/start of the 
CyberRow air conditioner by remote source.

MAIN POWER SERVICE SWITCH

The CyberRow unit shall be provided with a unit mounted 
main power service switch.

 

SERIES CONTROLLER

GENERAL

The advanced microprocessor based 

 Series controller 

shall be equipped with fl exible software capable of meeting 
the specifi c needs of the application. The setpoints shall be 
default and their ranges shall be easily viewed and adjusted 
from the user interface display. The program and operating 
parameters shall be permanently stored on a non-volatile 
system in the event of power failure.  The controller shall be 
designed to manage temperature to a user defi ned setpoint 
via control output signals to the CyberRow unit.  

The controller shall receive inputs for measurable control 
conditions (temperature, relative humidity, and dew point) via 
return air or remote mounted supply air sensors. The internal 
logic will then determine if the conditions require cooling. 
Control setpoints shall be established to maintain design 
conditions of the installation. The controller will respond 
accordingly to changes in these conditions and control the 
output/demand for the appropriate mode of operation until 
user defi ned conditions are achieved.

FIELD CONFIGURABLE

The program for the 

 Series controller shall be fi eld 

confi 

gurable, allowing the operator the capability of 

selecting control setpoints specifi c to the application. 
Operator interface for the 

 controller is provided via a door 

mounted user interface display panel. The display panel shall 
have a backlit LCD graphical display and function keys giving 
the user complete control and monitoring capability of the 
precision cooling system. The menu driven interface shall 

Содержание CyberRow DX CRS-042-AR

Страница 1: ...1 STULZ USA All rights reserved QEWR002G CYBERROW DX ENGINEERING MANUAL CyberRow DX Row Based Precision Air Handling Units 12kW 33kW 60 Hz DX Air Water Glycol Floor Mounted Systems Engineering Manual...

Страница 2: ...tions GLOBAL LEADER From our beginnings in Germany 70 years ago to our expansionthroughouttheworld STULZisalwaysinnovating Today STULZ has seven global production plants and hundreds of sales and serv...

Страница 3: ...ING MANUAL Table of Contents Model Nomenclature 4 Model Features 4 Model Nomenclature Speci cations 5 Con gurations 6 Product Features 7 Technical Data 8 10 Electrical Data 11 Sound Data 11 Dimensiona...

Страница 4: ...ustry 12 and 24 cabinet widths 3 EC Fans Independently and in nitely adjustable EC fans ensure maximum ef ciency Used in containment open architecture and hot spot reduction applications Adapts to bot...

Страница 5: ...nstalled head pressure waterregulating controlvalve s Condenser source water shall be provided by a cooling tower or some other remote water source Head Pressure Control Head pressure shall be automat...

Страница 6: ...om IT equipment and prevents from mixing with cool air The front of IT equipment is accessed in the external cold aisle The STULZ CyberRow draws the contained hot air from the hot aisle removes the he...

Страница 7: ...dard Dual Power Connection N A N A N A Remote Stop Start Contacts Standard Standard Standard Main Power Switch Standard Standard Standard E MICROPROCESSOR CONTROLLER A C Grouping pLAN Interface Option...

Страница 8: ...8 4 5 8 Face Velocity fpm 260 500 500 Compressor Heat pump duty rated Scroll R410A Type Qty Scroll 1 Scroll 1 Scroll 1 Watts Input 3 680 7 090 7 830 Tot Heat of Rej MBH 64 6 124 131 8 Condenser Type R...

Страница 9: ...ing 2 Way Water Valve Optional Control Modulating 3 Way Water Valve Compressor Heat pump duty rated Scroll R410A Type Qty Watts Input 2 820 3 940 5 690 7 470 6 290 8 250 Tot Heat of Rej MBH 66 64 128...

Страница 10: ...92 98 106 96 Total KW 14 3 15 4 14 0 27 4 29 7 26 8 29 31 28 Sensible 14 3 15 4 14 0 27 4 29 7 26 8 29 31 28 90 FDB 66 1 FWB Entering Air Temperature Total MBH 46 50 45 88 97 88 93 102 91 Sensible 46...

Страница 11: ...614 speci es a method for measuring the component of sound intensity that is normal to a measurement surface The measurement surface is chosen to enclose the noise source s so that the sound power lev...

Страница 12: ...PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION 11 6 77 8 42 1 CONDENSATE CONNECTION PIPING CONNECTION POWER CONNECTION AIROUT AIRIN AIR OUT AIR OUT AIR IN AIR IN POWER POWE...

Страница 13: ...tandards of quality management to ensure product quality Each system shall be subjected to a complete operational and functional test procedure at the factory prior to shipment CABINET Side access pan...

Страница 14: ...Flooded Control AR The air cooled system shall incorporate a low ambient ooded head pressure control The pressure control shall be for year REFRIGERATION SYSTEM All piping and components contained wi...

Страница 15: ...ach high voltage circuit shall be individually protected by circuit breakers or manual motor starters on all three phases The blower motor shall have thermal and short circuit protection Line voltage...

Страница 16: ...creens PASSWORD PROTECTION Access to the Info Menu Alarms Log and the ability to monitor room conditions shall be allowed without the use of a password Modi cations to the control setpoints shall requ...

Страница 17: ...20 ft long remote strip cable type water and leak detector shall be provided for remote eld installation Upon sensing a water leak the normallyclosedwaterdetectorcontrol circuit shall open thereby sh...

Страница 18: ...18 QEWR002G STULZ USA All rights reserved CYBERROW DX ENGINEERING MANUAL NOTES...

Страница 19: ...19 STULZ USA All rights reserved QEWR002G CYBERROW DX ENGINEERING MANUAL NOTES...

Страница 20: ...28918 Legan s Madrid STULZ France S A R L 107 Chemin de Ronde 78290 Croissy sur Seine info stulz fr STULZ S p A Via Torricelli 3 37067 Valeggio sul Mincio VR STULZ CHSPL India Pvt Ltd 006 Jagruti Ind...

Отзывы: