SMOKE DETECTION
A photo-electric smoke detector shall be factory installed
and wired in the evaporator section of the suction side of
the evaporator blower. The air conditioner will shut down
upon sensing smoke in the return air stream.
FIRESTAT
The air conditioner shall be provided with a factory wired
and mounted fi restat. The fi restat will shut down the air
conditioner upon sensing a high return air temperature.
REMOTE WATER DETECTOR: SPOT TYPE
A remote single point water and leak detector shall
be factory supplied and shall ship separately for fi eld
installation. Upon sensing a water leak, the normally closed
water detector control circuit shall open, thereby shutting
down the CyberRow® unit’s water producing components.
REMOTE WATER DETECTOR: STRIP TYPE
A 20 ft. long remote strip/cable type water and leak detector
shall be provided for remote fi eld installation. Upon sensing
a water leak, the normally closed water detector control
circuit shall open, thereby shutting down the CyberRow®
unit’s water producing components.
CODE CONFORMANCE
The unit shall be designed and built to conform to UL STD
1995, certifi ed to CAN/CSA C22.2 No. 236. and listed with
ETL.