Stulz CyberRow CRS-090-C Скачать руководство пользователя страница 10

10

(Note:  All sound testing is performed in accordance to ISO 9614-2 Determination of Sound Power Levels.  
ISO 9614-2 Specifi es a method for measuring the component of sound intensity normal to a measurement 
surface which is chosen so as to enclose the noise source(s) of which the sound power level is to be deter-
mined.

)

Sound Data

CRS-090-C

Sound Pressure

LpA, free 

fi

 eld (dBA) in a 121.13 ft² (3.43m³) room at 

3.28 (1.0m) distance

Fan 
Speed %

Air

fl

 ow 

(SCFM)

63

125

250

500 1000 2000 4000 8000

Total 

dBA

NR 

Value

50%

1800

15.8 19.7 31.3 35.0 38.8

35.1

25.3

10.9

42.0 39

75%

2150

13.1 41.6 42.7 45.2 48.1

46.2

38.5

23.4

52.6 48

100%

2900

19.6 47.2 49.8 51.4 53.6

51.7

45.0

30.6

58.4 54

Fan 
Speed %

Air

fl

 ow 

(SCFM)

CRS-180-C

Sound Pressure

LpA, free 

fi

 eld (dBA) in a 146.91 ft² (4.16m³) room at 

3.28 ft (1.0m) distance

50%

4100

29.4 42.5 46.6 48.6 52.3

52.5

41.5

26.1

57.0 54

75%

5000

34.9 49.7 57.3 59.7 62.8

60.5

56.0

40.3

67.0 63

100%

5800

43.0 52.6 61.5 64.0 67.0

64.2

59.6

45.8

71.1 67

(Note:  Standard 1 KAIC rating, optional 65 KAIC rating available.)

Electrical 

Data

CRS-090-C

CRS-180-C

FLA

MCA

MFS

FLA

MCA

MFS

COOLING ONLY

120/1/60

8.3

10.4

15

N/A

N/A

N/A

208/1/60

5

6.2

15

N/A

N/A

N/A

208/3/60

5

6.2

15

9.3

11.6

15

460/3/60

2.5

3.2

15

4.5

5.6

15

575/3/60

2.1

2.7

15

3.7

4.6

15

COOLING AND HUMIDIFIER

120/1/60

N/A

N/A

N/A

N/A

N/A

N/A

208/1/60

N/A

N/A

N/A

N/A

N/A

N/A

208/3/60

N/A

N/A

N/A

18.5

23.2

25

460/3/60

N/A

N/A

N/A

8.7

10.9

15

575/3/60

N/A

N/A

N/A

7.1

8.9

15

ELECTRICAL AND SOUND  DA

TA

CyberRow®

Содержание CyberRow CRS-090-C

Страница 1: ...1 STULZ CyberRow Engineering Manual Engineering Manual EM 13 77 kW Chilled Water Row Based Data Center Cooling Utilizing EC Fan Technology 60 Hz Data Indoor Cooling Row...

Страница 2: ...utstanding customer service make STULZ the perfect choice for all your environmental control needs ISO 9001 Quality Registered STULZ is committed to satisfying customer expectations by meeting and exc...

Страница 3: ...nclature 4 CyberRow Features 5 Configurations 6 Technical Data 7 Performance Data 8 Electrical and Sound Data 10 Dimensional Data 11 Standard Product Features 13 Product Guide Specifications 14 Chille...

Страница 4: ...4 MODEL NOMENCLATURE CyberRow Row Based System Nominal Capacity in 1 000 of BTU H CyberRow System Chilled Water System CRS 180 C CyberRow...

Страница 5: ...nd infinitely adjustable EC fans ensure maximum efficiency Used in containment open architecture and hot spot reduction applications Adapts to both high and low density IT environments Wide range of c...

Страница 6: ...om mixing with cool air The front of IT equipment is accessed in the external cold aisle The Stulz CyberRow draws the contained hot air from the hot aisle removes the heat and supplies cooled air into...

Страница 7: ...ntity of Blowers 3 3 Drive Method Direct Direct Humidification Electrode Steam Canister Humidifier with Adjustable Output Optional Lbs Hr kW Input N A 5 1 7 Std Control N A Proportional Washable Filte...

Страница 8: ...5 80 417 23 5 13 7 6 8 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 108 988 31 9 108 988 31 9 22 1 14 0 12 F T 103 324 30 3 103 324 30 3 17 5 9 7 45 F EWT 10 F T 96 139 28 2 96 139 28 2 19...

Страница 9: ...3 4 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 221 108 64 7 204 623 59 9 46 2 29 8 12 F T 207 922 60 9 199 053 58 3 36 2 19 6 45 F EWT 10 F T 177 357 51 9 177 357 51 9 37 4 20 3 12 F T 1...

Страница 10: ...51 4 53 6 51 7 45 0 30 6 58 4 54 Fan Speed Airflow SCFM CRS 180 C Sound Pressure LpA free field dBA in a 146 91 ft 4 16m room at 3 28 ft 1 0m distance 50 4100 29 4 42 5 46 6 48 6 52 3 52 5 41 5 26 1 5...

Страница 11: ...NNECTION POWER CONNECTION AIR OUT AIR OUT AIR IN AIR IN POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION POWER POWER CONNECTIONS CO...

Страница 12: ...Panel Option HUMIDIFIER HUMIDIFIER CONNECTIONS CONNECTIONS POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION AIR IN AIR IN AIR OUT...

Страница 13: ...Valve Optional Optional Electrode Steam Canister Humidifier N A Optional ELECTRICAL SYSTEM 16 Automatic Dual Power Transfer Switch Optional Optional Remote Stop Start Contacts Standard Standard Main...

Страница 14: ...fins with enhanced fin design for maximum heat transfer and STULZ CyberRow 13 77 kW Row Based Precision Control Air Conditioners Chilled Water Systems SUMMARY This specification describes requirements...

Страница 15: ...e loop and be securely fastened by an approved method Each wire in the unit shall be numbered for ease of service tracing All electrically actuated components shall be easily accessible from the front...

Страница 16: ...ult and their ranges shall be easily viewed and adjusted from the user interface display The program and operating parameters shall be permanently stored on a non volatile system in the event of power...

Страница 17: ...operate using the setpoints programmed by the factory The customer may enter new operating parameters in the Control menu and the system will then operate accordingly The new setpoints may be stored a...

Страница 18: ...be factory supplied and shall ship separately for field installation Upon sensing a water leak the normally closed water detector control circuit shall open thereby shutting down the CyberRow unit s w...

Страница 19: ...19 Chilled Water NOTES...

Страница 20: ...m STULZ Air Technology Systems Inc 1572 Tilco Drive Frederick Maryland 21704 Phone 301 620 2033 Fax 301 662 5487 E mail info stulz ats com www STULZ com STULZ mission is to be the premier provider of...

Отзывы: