CABINET

Side access panels shall be fabricated from 20 gauge 
galvannealed steel and shall be securely bolted to a 14 
gauge base and the top plate. The top plate, front and rear 
panels shall be  fabricated from 16 gauge galvannealed 
steel. The cabinet shall be powder coated with a satin 
black fi nish to provide durability, and to protect from 
corrosion. Armafl ex elastomeric thermal insulation shall 
be used to insulate the cabinet, block noise and prevent 
damage from vibration. Casters and leveling feet shall be 
included to ease the installation and level the equipment 
with existing IT solutions.

AIRFLOW PATTERNS

All units shall be designed using a front discharge with 
a rear return airfl ow pattern. An optional plenum with a 
front diverted discharge pattern is available.

AIR FILTRATION

All units shall be equipped with removable, washable 
fi lters. These fi lters shall consist of an open cell structured 
polyurethane foam with a roll formed 3000 series 
aluminum frame. Filters shall meet both UL 900 and UL 
94 HF-1 standards.

MECHANICAL COMPONENTS

BACKWARD INCLINED, PLENUM STYLE FAN, 
WITH AN EC MOTOR

The blowers shall be backward inclined plenum style 
fans with an Electronically Commutated (EC) motor, 
for maintenance free operation. The motor shall 
include: integrated electronic control board and direct 
microprocessor control signaling for fan speed control, 
soft-starting capabilities, and integrated current limitations. 
Each fan shall be low noise, low vibration manufactured 
with an anti-corrosive aluminum impeller.  Each fan 
impeller shall be dynamically and statically balanced in two 
planes to minimize vibration during operation.

CHILLED WATER COOLING COIL

The coil shall be constructed of seamless drawn copper 
tubes, mechanically bonded to tempered aluminum fi ns 
with enhanced fi n design for maximum heat transfer, and 

STULZ CyberRow®

13 - 77 kW Row-Based

Precision Control Air Conditioners Chilled 

Water Systems

SUMMARY

This specifi cation describes requirements for a precision 
environmental control system.  The STULZ CyberRow® is 
a row-based cooling system that shall provide precision 
temperature control (and humidity control for the 
24” model) for computer rooms or rooms containing 
telecommunications or other highly sensitive heat load 
equipment where continuous 24 hour a day, 365 days a 
year air conditioning is required.  

Designed with both front and rear access, CyberRow® 
systems require minimum fl oor space. The supplied system 
shall be provided with ETL Certifi cation. The CyberRow® 
model number shall be, CRS-     - .

DESIGN REQUIREMENTS

The environmental control system shall be a STULZ 
CyberRow® Chilled Water factory-assembled unit. The 
unit shall be designed for a row-based installation with 
removable front and rear access panels.  No allowance for 
side service access shall be required, however removable 
side access panels shall be provided for additional access.  

The CyberRow® units are especially adapted for both 
raised and unraised fl oors. The air handling section shall 
be specifi cally designed for high sensible heat ratio. Each 
system shall be capable of handling        CFM at        inches 
of water external static pressure.  The unit shall have the 
cooling capacity of        BTU/H, and the sensible cooling 
capacity of        BTU/H based on entering air condition of        
°F dry bulb and       °F (°C) wet bulb.  The humidifi er (only 
available in the 24” unit) shall have the capacity of 5 Lbs/hr. 
The main fan motors shall be        HP. The unit shall have a 
power supply of        volts.

QUALITY ASSURANCE

The manufacture shall maintain a set of international 
standards of quality management to insure product quality. 
Each system shall be subjected to a complete operational 
and functional test procedure at the factory prior to 
shipment. 

14

PRODUCT GUIDE SPECIFICA

TIONS

CyberRow®

Содержание CyberRow CRS-090-C

Страница 1: ...1 STULZ CyberRow Engineering Manual Engineering Manual EM 13 77 kW Chilled Water Row Based Data Center Cooling Utilizing EC Fan Technology 60 Hz Data Indoor Cooling Row...

Страница 2: ...utstanding customer service make STULZ the perfect choice for all your environmental control needs ISO 9001 Quality Registered STULZ is committed to satisfying customer expectations by meeting and exc...

Страница 3: ...nclature 4 CyberRow Features 5 Configurations 6 Technical Data 7 Performance Data 8 Electrical and Sound Data 10 Dimensional Data 11 Standard Product Features 13 Product Guide Specifications 14 Chille...

Страница 4: ...4 MODEL NOMENCLATURE CyberRow Row Based System Nominal Capacity in 1 000 of BTU H CyberRow System Chilled Water System CRS 180 C CyberRow...

Страница 5: ...nd infinitely adjustable EC fans ensure maximum efficiency Used in containment open architecture and hot spot reduction applications Adapts to both high and low density IT environments Wide range of c...

Страница 6: ...om mixing with cool air The front of IT equipment is accessed in the external cold aisle The Stulz CyberRow draws the contained hot air from the hot aisle removes the heat and supplies cooled air into...

Страница 7: ...ntity of Blowers 3 3 Drive Method Direct Direct Humidification Electrode Steam Canister Humidifier with Adjustable Output Optional Lbs Hr kW Input N A 5 1 7 Std Control N A Proportional Washable Filte...

Страница 8: ...5 80 417 23 5 13 7 6 8 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 108 988 31 9 108 988 31 9 22 1 14 0 12 F T 103 324 30 3 103 324 30 3 17 5 9 7 45 F EWT 10 F T 96 139 28 2 96 139 28 2 19...

Страница 9: ...3 4 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 221 108 64 7 204 623 59 9 46 2 29 8 12 F T 207 922 60 9 199 053 58 3 36 2 19 6 45 F EWT 10 F T 177 357 51 9 177 357 51 9 37 4 20 3 12 F T 1...

Страница 10: ...51 4 53 6 51 7 45 0 30 6 58 4 54 Fan Speed Airflow SCFM CRS 180 C Sound Pressure LpA free field dBA in a 146 91 ft 4 16m room at 3 28 ft 1 0m distance 50 4100 29 4 42 5 46 6 48 6 52 3 52 5 41 5 26 1 5...

Страница 11: ...NNECTION POWER CONNECTION AIR OUT AIR OUT AIR IN AIR IN POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION POWER POWER CONNECTIONS CO...

Страница 12: ...Panel Option HUMIDIFIER HUMIDIFIER CONNECTIONS CONNECTIONS POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION AIR IN AIR IN AIR OUT...

Страница 13: ...Valve Optional Optional Electrode Steam Canister Humidifier N A Optional ELECTRICAL SYSTEM 16 Automatic Dual Power Transfer Switch Optional Optional Remote Stop Start Contacts Standard Standard Main...

Страница 14: ...fins with enhanced fin design for maximum heat transfer and STULZ CyberRow 13 77 kW Row Based Precision Control Air Conditioners Chilled Water Systems SUMMARY This specification describes requirements...

Страница 15: ...e loop and be securely fastened by an approved method Each wire in the unit shall be numbered for ease of service tracing All electrically actuated components shall be easily accessible from the front...

Страница 16: ...ult and their ranges shall be easily viewed and adjusted from the user interface display The program and operating parameters shall be permanently stored on a non volatile system in the event of power...

Страница 17: ...operate using the setpoints programmed by the factory The customer may enter new operating parameters in the Control menu and the system will then operate accordingly The new setpoints may be stored a...

Страница 18: ...be factory supplied and shall ship separately for field installation Upon sensing a water leak the normally closed water detector control circuit shall open thereby shutting down the CyberRow unit s w...

Страница 19: ...19 Chilled Water NOTES...

Страница 20: ...m STULZ Air Technology Systems Inc 1572 Tilco Drive Frederick Maryland 21704 Phone 301 620 2033 Fax 301 662 5487 E mail info stulz ats com www STULZ com STULZ mission is to be the premier provider of...

Отзывы: