like this the Auxiliary Contact works with the lowest set condition and stops when it 
has reached the highest programmed condition through charging. 
Example: start of a generator with the HP-COMPACT 
In order to program the auxiliary contact to start at 25% and to stop at 75% of the 
battery state-of-charge, here is the procedure to follow: 

  Press the key AUX. CONTACT (Program) 21 during at least 2 seconds. Then 

the states will be displayed blinking (factory settings LED’s 10/11/12/13). As 
these states are not wished for the start of the generator, they must be disabled. 

  With the key (select) 20, select the LED’s to disable (the active LED’s are 

blinking) and disable them with the key 19 Change Status. Select the other 
LED’s to switch off with the key (select) 20 and switch them off with the key 19 
Change Status until all are disabled. 

  Then select the LED 17 with the key (select) 20 and activate the contact with the 

key 19 Change Status. The generator will start once the LED 17 switches of.  

  Then select the LED 16 with the key (select) 20 and activate the contact with the 

key 19 Change Status. The generator will stop once the LED 16 switches on.  

  If no key is activated during 30 seconds, the normal operation states are 

displayed automatically again. 

For a control the key Program can be pressed at least 2 seconds. The values set are 
displayed blinking. 
As per the inverter output power (not available with some special executions) 
Activating the auxiliary contact for the generator start can be programmed also on a 
pre-determined output power of the inverter. The auxiliary contact will be activated if 
the inverter output power exceeds 80% of the inverter nominal power during 3 
minutes and/or 100% during 30 seconds.  
The auxiliary contact will remain activated 30 minutes after the input current has 
come back to a value lower than the one adjusted by the “INPUT LIMIT” (chap. 
4.6.4). In other words, the contact will be deactivated 30 minutes after the lighting out 
of the LED 200%. 
This programming is achieved accordingly to chap. 5.4.2 of the user manual and by 
activating the contact on LED 100% of “Power Monitor” (25). 

5.4.4  Power cut of the second priority loads 
The auxiliary contact can also be used to cut the power of less priority loads when 
the battery state of charge is lower than a given threshold. In that case, only one of 
the battery state of charge, or the “transfer” function will be programmed as power cut 
criteria. 
The second priority loads will be supplied only when the generator is ON or when the 
battery has a sufficient threshold. 

5.4.5 Manual operating of Auxiliary Contact 
The Auxiliary Contact can be operated at any time with the Push Button 21 (AUX. 
CONTACT). The LED 6 „Contact manual“ lights up as information that the Contact is 
manually operated, and LED 5 „Contact active“ lights up when the Contact is active. 
By pushing the Push Button 21 a second time, the Contact is disabled. By pushing it 
the third time, automatic functions are restored. 

Содержание HP-COMPACT HPC 2800-12

Страница 1: ...50 Sion E MAIL info studer innotec com User s and installer s Manual Sine wave Inverter Battery charger Transfersystem HP COMPACT HPC 2800 12 HP COMPACT HPC 4400 24 HP COMPACT HPC 6000 48 HP COMPACT HPC 8000 48 Remote control RCC 01 Remote Power sharing RPS 01 Temperature sensor CT 35 ...

Страница 2: ...ing 11 3 6 Pre installation settings 11 4 Control 14 4 1 Display and control parameters 14 4 2 Light Emitting Diodes LED 15 4 3 Push buttons 16 4 4 Turning Knobs 16 4 5 The Inverter 16 4 6 The battery charger 18 4 7 The Transfer system 20 4 8 The Multifunctional Contact 21 4 9 The Remote Control RCC 01 22 4 10 The Temperature sensor CT 35 22 4 11 Remote control for Power Sharing RPS 01 23 5 Progra...

Страница 3: ...irm and established procedures Every HP COMPACT has its own serial number which helps to refer back to its original data in the event of controls or repairs That is why you should never remove the identification plate showing the serial number The production assembly and tests on all HP COMPACT appliances are totally carried out in our company in Sion Switzerland The warranty for these appliances ...

Страница 4: ...ried out by skilled and trained people The whole installation connected with the HP COMPACT must comply with the rules and codes in force People without the written authorization from STUDER INNOTEC are strictly forbidden to carry out any change or repair on the appliances For authorized changes only original parts are to be used The HP COMPACT may only be used when it has been installed in accord...

Страница 5: ...teries all personal metal items such as rings necklaces and bracelets must be removed Batteries are so powerful that short circuit with these items can melt them and thus cause severe burns Always follow the battery manufacturer instructions Under certain conditions HP COMPACT or a connected generator can start automatically While working on an electrical installation you must ensure that these ap...

Страница 6: ...e side you have an alternating voltage at the output for the use of consumer appliances On the other side the battery park is being charged The distribution of energy between the consumer appliances and battery charger is automatic 2 2 3 The battery charger The built in battery charger is so designed that it can charge the battery quickly and fully A microprocessor controlled Step charging process...

Страница 7: ...of 2V 6V or 12V In most cases to generate the necessary operating voltage and the capacity of the batteries for the HP COMPACT many batteries have to be connected together in parallel and or in series Here are 3 examples of connection 2 3 1 Connection in parallel 2 3 2 Serial connection 2 3 3 Serial and parallel connection ...

Страница 8: ...rminals AC INPUT and AC OUTPUT must be carried out with a screwdriver Nr 3 and the connection of the AUX RELAY terminal with a screwdriver Nr 2 The conductor cross section on the terminals AC INPUT AC OUTPUT must comply with the local rules All connecting cables and also the battery cables must be fixed with strain relief clamps The fuses supplied with the HPC 4400 24 6000 48 and 8000 48 have to b...

Страница 9: ...Pass through hole for RCC 01 CT 35 and RPS 01 N Protection Thermal circuit breaker 30A 50A for HPC 8000 48 for the Transfer system 3 5 Cabling Connecting the HP COMPACT is a very important step of the installation You must take care that all connection work is carried out in a clean and correct way and that under no circumstance a cable is connected to a wrong terminal Connecting of the HP COMPACT...

Страница 10: ...ies ready for connection suitable terminals fuse on one of the connection points cable in good shape with if necessary terminals rightly set Mount the red cable on the positive pole and the black cable on the negative pole of the battery While connecting the second cable a spark due to the charge of the capacities at the input stage is normal In the same time an acoustic signal tells that the cont...

Страница 11: ...elay in the non active mode 3 6 5 Connection to Remote control The Remote Control RCC 01 is connected in the terminal marked Remote control with a 20m long cable and a RJ11 8 connector The Remote Control can be plugged IN or plugged OUT during any operation situation Push in the connector softly until you hear the click showing that the connector is locked The same applies to the plug in the Remot...

Страница 12: ...STUDER INNOTEC HP COMPACT HP COMPACT V5 4 14 80 4 Control 4 1 Display and control parameters ...

Страница 13: ...7 TRANSFER Transfer system is active In coming voltage is being sent directly to AC OUT outlet Transfer bypass is disabled see chap 4 7 8 AC OUT There is a voltage at the AC OUT outlet The Inverter is in Standby Mode 9 INVERTER Inverter is working Forced Inverter Mode see chap 4 5 10 Over Temp For the time being the HP COMPACT is out of service because of overheating 11 Overload The HP COMPACT is ...

Страница 14: ...vides up to 3 times the nominal power to start motors The Inverter mode is displayed through LED 9 Inverter If the Inverter Mode is disabled see chap 5 5 LED 9 will blink If the LED 9 is lit the Inverter is in operation and you have 230Vac at the output AC OUT The actual power of the connected appliance is displayed on the power monitor 25 and on the Remote Control 4 5 1 Charge detection system St...

Страница 15: ...aging That is why the battery condition is continuously controlled and supervised With low volt age the inverter switches off The LED 12 L H Batt is lit and the LED 13 OFF blinks When the battery voltage gets up to 12 1V 24 2V 48 4V the Inverter switches on automatically One minute before the Inverter switches off due to low voltage it gives out an acoustic alarm signal If the Auxiliary Contact ha...

Страница 16: ...y supplied with power LED 8 AC OUT is lit The charger functions are shown in the following diagram 4 6 2 Default values for battery voltage thresholds Low voltage Float charge Absorption Equalization Absorption time Equalization time 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V 12 24 48V 12 24 48V 11 6 23 2 46 4 13 5 27 0 54 0 14 4 28 8 57 6 15 6 31 2 62 4 2h 20 These values can be modified by ...

Страница 17: ...cannot limit the current then the generator means to stop or the circuit breaker means to break before 4 6 5 Set the INPUT LIMIT 26 The current available for the HP COMPACT depends on the supply used from a motor generator the network of a camping or of a shore connection The value of the turning knobs INPUT LIMIT 26 must be adjusted lower or equal to the current available from the source For exam...

Страница 18: ...battery charger is in the section Programming Chap 5 3 The correct charging is mandatory for a safe function and a long life of the battery The battery charger are described by the graphic in chap 4 6 1 4 7 The Transfer system When an AC voltage is at the input AC IN of the HP COMPACT the LED 1 AC IN is lit When this voltage matches the lowest adjusted value set by the Turning Knob 23 TRANSFER and...

Страница 19: ... break free alternating voltage for the appliance A quick transfer switch is not always sensitive nor is it always desired For example when the appliances are operated by a small back up generator An overload of a short period on such a generator i e start of a vacuum cleaner etc has the effect of decreasing the voltage for a short time As in such cases the transfer to the Inverter is not desired ...

Страница 20: ...ontrol The Programming is described in the section Programming The output power and the charging currents are displayed on the Remote Control In the Remote Control there is an additional Alarm Contact and a built in Control Input These two functions are available through Tip jack RJ11 4 for use This Auxiliary Contact is Front Work Contact max 0 5A which is independent from the Auxiliary Contact of...

Страница 21: ...of 6A Caution the HP COMPACT will not limit if an appliance draws more current than available from the source This means that the connected generator will be over loaded or that the circuit breaker before the HP COMPACT will break 5 Programming The HP COMPACT except for 60Hz versions is equipped with a Flash processor fitted out with EEPROM Memory which means that even when it is disconnected from...

Страница 22: ...d These four red LED s show the function set Low voltage LED 13 ON OFF Float charge LED 12 Batt Low high Absorption End of charge LED 11 Overload Equalization LED 10 Overtemp Absorption Time LED 10 11 12 13 altogether With the Push Button 19 Change status set the desired parameter voltage or time to modify LED 14 15 16 17 18 Push Button 19 Change status to set the desired value according to the ta...

Страница 23: ...work of the contact meets that of the logic OR Function 5 4 2 The programming of the Auxiliary Contact The programming of the Auxiliary Contact is carried out in the following Steps The Push Button 21 Program presses down for min 2 seconds The LED 4 Program is lit as an indication that the HP COMPACT is in program mode A blinking LED shows the programmed condition for the auxiliary contact LED 10 ...

Страница 24: ...er the inverter output power not available with some special executions Activating the auxiliary contact for the generator start can be programmed also on a pre determined output power of the inverter The auxiliary contact will be activated if the inverter output power exceeds 80 of the inverter nominal power during 3 minutes and or 100 during 30 seconds The auxiliary contact will remain activated...

Страница 25: ...hich mode is disabled 5 5 1 Diagram of the different modes Shows an off LED Shows a blinking LED Shows a lighted LED All the functions are enabled This is the factory setting The inverter is disabled Only the transfer switch and the charger will work normally Inverter and charger are both disabled Only the transfer switch function is ena bled in input voltage and frequency is OK Charger and transf...

Страница 26: ...STUDER INNOTEC HP COMPACT HP COMPACT V5 4 28 80 8 Technical Data ...

Отзывы: