6  TECHNICAL SPECIFICATION

Stuart Turner reserve the right to amend the specification in line with its policy of 
continuous development of its products.

*Note:  The maximum pressure that can be applied to the pump under any   

 

 

installation conditions.

6.11 

Noise:  

The equivalent continuous A-weighted sound pressure level at a  

 

 

distance of 1 metre from the pump does not exceed 70 dB(A).

Pump Model

MBF 60-1-15

46631

MBF 80-1-15

46634

General

Guarantee

3 years

WRAS approval

1412081

Features

Pump type

Peripheral

Mechanical seal

EPDM / PTFE / Al. Oxide

Flexible hoses

2

2

Diaphragm tank size

60 litre

80 litre

Diaphragm tank water capacity

30 litre

40 litre

Dry run protection

ü

ü

Materials

Pump body

Brass

Impeller

Brass

Performance

Maximum head (closed valve)

3.2 bar

Maximum flow

16 l/min

Maximum working pressure*

450 kPa (4.5 bar)

Maximum ambient air temperature

40 

o

C

Min / Max water temperature

Min 4 

o

C / Max 35 

o

C

Flow switch sensitivity (approx)

0.6 l/min

Connections

Pump connections

G ¾ male

Flexible hoses

Connections

G ¾ female x 15 mm push-in x 200 mm long

Motor

Type

Induction, auto-reset thermal trip

Duty rating

Continuous

Electrical

Power supply / phase / frequency

230 V a.c. / 1 / 50 Hz

Current (full load)

1.7 Amps

Power consumption

365 Watts

Fuse rating

5 Amps

Power cable (pre-wired)

1.5 metres

Physical

Enclosure protection

IPX4

Length

480 mm

Width

457 mm

Height (excluding hoses)

663 mm

852 mm

Dry Weight (including fittings)

17.6 Kg

21.8 Kg

Filled Weight (maximum)

46.6 Kg

60.8 Kg

Содержание mainsboost MBF 60-1-15

Страница 1: ...oklet with the owner as it contains important guarantee maintenance and safety information MBF 60 1 15 Pt No 46631 MBF 80 1 15 Pt No 46634 Read this manual carefully before commencing installation Thi...

Страница 2: ...and operating instructions in this booklet must be followed z z The pump must not be used for any other application without the written consent of Stuart Turner Limited z z The pump must be installed...

Страница 3: ...le free service Failure to install the unit in accordance with the installation instructions will lead to invalidation of the warranty STORAGE If this product is not to be installed immediately on rec...

Страница 4: ...uge 2 Flexible hoses 2 Valve strainer check valve combined 1 Pressure regulating valve 1 Adapter G to G 1 A B C D E F Fig 1 IMPORTANT With the pump removed from its packaging check for any damage prio...

Страница 5: ...emoved prior to pump installation flux damage will void any warranty 1 15 Pipework design Care should be taken in the design of pipework runs to minimize the risk of air locks e g use drawn bends rath...

Страница 6: ...casing can become very hot under normal operating conditions Care must be taken to ensure it cannot be touched during operation 2 15 Water retention Site the pump in a location where in the unlikely e...

Страница 7: ...check valve must be fitted c It is advisable to fit a bypass pipe and isolating valves This will allow removal of the pump for maintenance and servicing and ensure the water supply into the property...

Страница 8: ...onnection unit should be mounted in an easily accessible position and should be labelled if confusion is possible to allow easy identification of the flomate isolating switch 3 17 Earthing This applia...

Страница 9: ...factory pattern is always maintained If the supply cord is to be changed or is damaged it must be replaced with a special cord assembly available from Stuart Turner or one of their approved repairers...

Страница 10: ...nce to re fill the vessel ready for next use 4 13 For Further Technical Support Phone the Stuart Turner PumpAssist team on 44 0 800 31 969 80 Our staff are trained to help and advise you over the phon...

Страница 11: ...30 litre 40 litre Dry run protection Materials Pump body Brass Impeller Brass Performance Maximum head closed valve 3 2 bar Maximum flow 16 l min Maximum working pressure 450 kPa 4 5 bar Maximum ambie...

Страница 12: ...ts Pump runs on when all terminal outlets are closed Leak in system Check tap washers w c valve washers pipe joints Reed clamp out of position Ensure reed clamp is fitted correctly in location groove...

Страница 13: ...ng this extent of movement If this does not happen this indicates a possible fault with the reed switch or the P C B which is located within the terminal box These should be checked electrically Consu...

Страница 14: ...ternal parts of the terminal box z z Briefly reconnect the mains power supply to the pump the power on light should illuminate if the pump has been correctly wired z z Isolate the mains electrical pow...

Страница 15: ...wear and tear and defects which have a negligible effect on the value or operation of the pump Reasonable evidence must be supplied that the product has been purchased within the guarantee term prior...

Страница 16: ...roduct launches and access to any special offers or promotions Following initial registration Stuart Turner offers a professional training programme enabling you to achieve Approved Installer status a...

Отзывы: