Operating and maintenance manual 

AG-CAB1035 Water softner 

Sivu 6/22

 

 

StrongFlow Oy 

Tel. +358 20 730 1820 

Domicile: Kaarina 

Ahokylänkatu 3 

www.strongflow.fi 

Business ID: 2024125-8 

FI-20780 Kaarina 

 

VAT no: FI25511181 

 

2.4 Brine tank and tube connection 

 

Brine tank should be installed to even platform. Connect brine tanks suction tube (picture 3) to air checks 

regenerant line connection. Before starting the filter that all connections are well prepared, and tubes / 

piping have no places for leakage. Possible leakage in brine suction line can cause premature closure of 

floating ball valve and excess brine left to bottom of brine tank.    

 

Drain  tube  must  be  installed  between  brine  tank  and  drain  to  further  damages  in  possible  overflow 

situation of brine tank. Attach tube to overflow fitting and run to drain (picture 4). 

 

 

 

 

 

 

 

 

 

 

 

Picture 3. Air check 

 

 

 

Picture 4. Overflow line connection

 

 

 

Содержание AG Series

Страница 1: ...NS 28 9 2018 StrongFlow Oy Domicile Kaarina Ahokylänkatu 3 Business ID 2024125 8 FI 20780 Kaarina VAT no FI25511181 StrongFlow Oy Ahokylänkatu 3 20780 Kaarina Y Tunnus 2024125 8 www strongflow fi 358 20 730 1820 AG 250 330 Water softeners ...

Страница 2: ...TROLLER INSTRUCTION 7 3 1 Controller display 7 3 2 Controller buttons 8 4 PROGRAMMING CONTROLLER 9 4 1 Initial power up Re initialization reset 9 4 2 Default settings 10 4 3 Additional settings P9 P19 14 4 4 Cycle time programming 15 4 4 1 Regeneration modes 15 4 4 2 Manual regeneration 15 5 START UP OF THE FILTER AND VALVE 16 6 MAINTENANCE AND TROUBLESHOOTING 17 6 1 Cleaning the automatic valve f...

Страница 3: ...m table 1 Table 1 Technical information The content of the delivery Pressure vessel diffusor with tube automatic valve drain tube resin Brine tank salt suction pipe salt suction hose regeneration salt Manual 250 330 Connections filter DN Flow rate l min 32 7 57 Capacity m3 dH 120 200 Resin l 38 65 Rinse water l rinse 350 470 Pressure index bar Working pressure min max bar Water temperature min max...

Страница 4: ... backwash water Please note that the filter creates 700 1300 litres of backwash water each time it regenerates 2 For electrical connections there must be grounded power outlet 230V 50Hz Use only the power AC adapter that is supplied 3 Make sure there is enough room around the filter for possible maintenance 4 Do not use filter or piping at temperatures above 40 C Filter should be protected from fr...

Страница 5: ...o be checked before filter is started 2 3 Water line connections Filters inlet and outlet fittings are internal thread Outlet fitting is marked with arrow Drain line fitting for 12 7 mm tube is pre installed to valves drain line connection by supplier Its recommended that bypass line is installed between inlet and outlet lines to allow detaching of filter for maintenance without interruptions in w...

Страница 6: ...ture 3 to air checks regenerant line connection Before starting the filter that all connections are well prepared and tubes piping have no places for leakage Possible leakage in brine suction line can cause premature closure of floating ball valve and excess brine left to bottom of brine tank Drain tube must be installed between brine tank and drain to further damages in possible overflow situatio...

Страница 7: ... 8 Not is use 9 Shows the set values e g current time time for regeneration etc 10 Separator for hours and minutes 11 Shows if value is locked When shown its not possible to change the value in case 12 Filter makes two regenerations in a row 13 Regeneration process is running 14 Not in use 15 Time and date for regeneration when controller is in normal mode and under programming 16 Current time and...

Страница 8: ...ure 6 Picture 6 Controller buttons 1 DOWN arrow Generally used to scroll down or increment through a group of choices 2 SET Used to accept a setting that normally becomes stored in memory Also used together with the arrow buttons 3 UP arrow Generally used to scroll up or increment through a group of choices 4 REGENERATE Used to command the controller to regenerate Also used to change the lock mode...

Страница 9: ...e start up can begin However do not open the inlet water valve yet 1 Connect AC adapter to power source picture 7 Make sure that the electric cord doesn t tangle around the camshaft Picture 7 Controller identification 2 Select right valve type from table 2 Select your valve type using UP and DOWN buttons Accept selected valve type with SET button 3 Select system size resin volume in tank from tabl...

Страница 10: ...e types and resin volumes 4 2 Default settings Use UP and DOWN buttons to increment through the available selections Press SET button to accept selected value or type 1 Set time of day Press DOWN Set the correct time of day and press SET 2 Set Day of week Press DOWN Set the correct day of week 1 Sunday 2 Monday 3 Tuesday etc Press SET Filter Valve type Resin volume AG 250 255 40 AG 330 255 65 AG 3...

Страница 11: ...ile Kaarina Ahokylänkatu 3 www strongflow fi Business ID 2024125 8 FI 20780 Kaarina VAT no FI25511181 3 Set time of regeneration Press DOWN Choose time of regeneration Press SET 4 Set days to regenerate OPTION 1 Press DOWN Set number of days between time clock regeneration regen frequency Default value is 3 Press SET ...

Страница 12: ... Press DOWN To change the controller to regenerate on specific days set the number of days between regeneration to zero 0 Press the SET button and the display will show a flashing cursor at the top under Sunday The day of week can be selected when the cursor is below it To toggle the day on off the triangular cursor must be below that day and flashing Press SET 5 Set salt amount Press DOWN Recomme...

Страница 13: ...ow Oy Tel 358 20 730 1820 Domicile Kaarina Ahokylänkatu 3 www strongflow fi Business ID 2024125 8 FI 20780 Kaarina VAT no FI25511181 6 Set capacity Press DOWN Automatic valve will count filter capacity automatically by systems resin volume and salt amount Don t chance settings Press SET ...

Страница 14: ...sed P17 Not used P18 Not used P value Parameter descriptopm Units Notes P9 Unit of measure 0 english 1 metric 0 12h 1 24h P11 Service interval months P12 Remote regen sw Delay s 0 none 1 salt check only 2 generate chlorine and check salt P14 Refill rate gpmx100 P15 Brine type gpmx100 0 variable reserve delay regen 1 fixed reserve delay regen 2 variable reserve immediate regeneration 3 fixed reserv...

Страница 15: ...lve that is used in AG CAB filters C0 Normal filtering stage not shown C1 Regeneration back wash C2 Suction of the brine C3 Slow flushing C4 Pressurizing prepared C5 Quick flushing C6 Backwash 2 only in valve 255 C7 Quick flush 2 only in valve 255 C8 Fill of brine tank with water Picture 8 regeneration cycles 4 4 2 Manual regeneration Manual regeneration can be done with two ways Option 1 Press th...

Страница 16: ... to automatic valve 5 When the filter is full of water the water starts to flow slowly to drain Inlet valve can now be fully opened Let the water flow to drain until it becomes clear 6 Fill the brine tank start up fill First the brine tank is filled with water about 10 cm from the bottom of the brine tank Then insert about 50 75 kg of clean regeneration salt to brine tank There needs to be enough ...

Страница 17: ...in 1 Close the inlet and outlet valves 2 Start the regeneration cycle manually see chapter 4 4 2 page 15 and wait until valve is in backwash stage C1 the filter is now unpressurized 3 Remover the electric power plug from valve and open remove the filters water line connections 4 Remove the automatic valve twist the valve right handed thread and plug the diffusor upper end of tube 5 Hose water insi...

Страница 18: ...rrect salt dosage was set b No salt in regenerant tank b Add salt No conditioned water after c Injector or screen plugged c Clean injector and screen regeneration d Air check valve closes prematurely d Put control momentarily in brine slow rinse C2 Replace or repair air check if needed Contact dealer Water taste salty Regeneration does not work normally Check brine draw and time of regeneration Co...

Страница 19: ...ns AG 250 330 water softeners Sivu 19 22 StrongFlow Oy Tel 358 20 730 1820 Domicile Kaarina Ahokylänkatu 3 www strongflow fi Business ID 2024125 8 FI 20780 Kaarina VAT no FI25511181 7 ATTACHMENTS Attachment 1 Automatic valve configuration ...

Страница 20: ...uctions AG 250 330 water softeners Sivu 20 22 StrongFlow Oy Tel 358 20 730 1820 Domicile Kaarina Ahokylänkatu 3 www strongflow fi Business ID 2024125 8 FI 20780 Kaarina VAT no FI25511181 Attachment 2 Exploded view and spare part list ...

Страница 21: ...g and maintenance instructions AG 250 330 water softeners Sivu 21 22 StrongFlow Oy Tel 358 20 730 1820 Domicile Kaarina Ahokylänkatu 3 www strongflow fi Business ID 2024125 8 FI 20780 Kaarina VAT no FI25511181 ...

Страница 22: ...g and maintenance instructions AG 250 330 water softeners Sivu 22 22 StrongFlow Oy Tel 358 20 730 1820 Domicile Kaarina Ahokylänkatu 3 www strongflow fi Business ID 2024125 8 FI 20780 Kaarina VAT no FI25511181 ...