Page 20
23/03/01
ASSEMBLY INSTRUCTIONS FOR: Ca 7s / BCa 7s
When connecting the burner, make sure the length of the burner cable is
such that when the burner door is opened it becomes disconnected.
IMPORTANT:
Flue-gas temperatures of below 160ºC can lead to
sooting of the flue, when entering a stone or brick
chimney. Where flue-gas temperatures are below
160ºC gross, specially adapted chimneys must be
available. If after the burner has been set, the flue-gas
temperature is too low, the baffles from the 3rd flue
pass can be taken out. If necessary, the 2nd flue pass
baffles can also be removed.
NB: Every change made to the flue baffles requires
re-commissioning of the burner settings.
Electrical connections must be carried out by qualified
personnel in accordance with instructions supplied.
Electrical leads and oil pipes should never be fastened to
the boiler casing.
In the interest of technical progress, we reserve the right
to undertake changes and improvements in production
without notification.
Please refer to ‘Operating and Maintenance’ information
for details on baffles and control panel information.