World Patents Pending ©AirSense Technology Ltd. 1999
ISSUE 2.4
Page 44
T E C H N I C A L
.
M A N U A L
Information Size
Product id of detector (see above)
byte
Version number of software
byte
Total number of detectors in data structures (n)
byte
Number of enabled detectors
byte
Reference enable flag
byte
Currently displayed detector
byte
the following data structures have n elements with n being the total number of
detectors as shown above the first element is detector 1, 2 etc
Bargraph level (0-10) bit 8 is set if in FastLearn
n bytes
Aux LED flag (0 = off, 1 = on)
n bytes
PreAlarm LED flag (0 = off, 1 = on)
n bytes
Fire LED flag (0 = off, 1 = on)
n bytes
Flow Fault LED flag (0 = off, 1 = high, 2 = low, 254 = flash)
n bytes
Head fault LED flag (0 = off, 1 = on, 254 = flash)
n bytes
Isolated LED flag (0 = off, 1 = on, 254 = flash)
n bytes
Separator LED flag (0 = off, 1 = on, 254 = flash)
n bytes
Battery fault flag (0 = off, 1 = on)
byte
Mains fault flag (0 = off, 1 = on)
byte
Dimmed display flag (0 = off, 1 = on)
byte
the following four data structures are transmitted n times with n being the total
number of detectors as shown above the first element is detector 1, 2 etc
Fire level (0-255)
byte
PreAlarm level (0-255)
byte
Aux level (0-255)
byte
Detector level (0-255)
byte
Selected detector
byte
Selected function
byte
Function value
byte
XOR sum of all data
byte
Extended remote monitor mode is not supported by the remote software but is
provided for other products that remotely access the Stratos range of detectors like
SenseNET™.
Remote monitor
format