World Patents Pending ©AirSense Technology Ltd. 1999
ISSUE 2.4
Page 38
T E C H N I C A L
.
M A N U A L
Remote control software
Stratos can be connected to any PC compatible using the remote control software and
the appropriate serial cable (connections for a suitable cable are given in the installers
handbook under the heading ‘Connection to a computer’).
The Stratos master asks for an access code upon pressing the carriage return button.
This access code is the same code that is entered in functions 01 and 02 on the
programmer on the back of the front panel.
The Stratos remote software is fully menu driven for ease of use and consists of three
major parts; setup menu, demonstration and log menu and diagnostic menu. These
are covered more fully below.
1.
Time and date
The time and date must be set correctly for the event log and chart recorder log. The
time is set in 24 hour format HH:MM and the date set in DD/MM/YY. Typing an invalid
time or date causes an error message to be printed followed by a prompt to enter the
data again.
2.
Detector
This menu sets the alarm levels and time delays, alarm factor and ClassiFire override.
The current setting is displayed followed by a prompt for a new value. Pressing enter
only will leave the value untouched.
3.
Alarm actions
This menu sets the detector actions taken after an alarm has occurred. Latching and
cascading alarms are set on this menu. The current setting of each functions shown
(either Yes or No), followed by a prompt to change it. Pressing enter on it’s own has
no effect on the current setting.
4.
Detectors
The number of detectors on the master is set with this function. This figure is
automatically set on default reset.
Using the remote
control software
Setup menu