T E C H N I C A L
.
M A N U A L
Stratos is provided with the facility to use a Reference signal to combat unwanted alarms
caused by smoke from outside sources drawn into a protected areas.
There are two methods of referencing; local and remote. The difference between local
and remote referencing is shown below.
Local and
remote
referencing
Both systems have a local reference, which is a slave detector
on the masters own slave
loop
that has a special address. Each master has its local reference (function 5) set to
‘y’ and its remote reference (function 6) set to ‘n’.
Master 1 still has a local reference, but
its reference is also used as the reference for
Master 2
and up to three additional masters. Master 2 must have local reference
(function 5) set to ‘n’ and remote reference (function 6) set to ‘y’.
H I G H S E N S I T I V I T Y S M O K E D E T E C T O R
TM
ISOLATE
TEST
RESET
S M O K E D E N S I T Y
AUX
FIRE
PRE-
ALARM
RENEW
OK
FAULT
OK
ISOL.
ON
FAULT
OK
HIGH
OK
LOW
1
2
3
4
Ref.
Air Flow
1
2
3
4
5
6
7
8
9
10
Detector
Power
Separator
Artificial Intelligence
With
S L A V E D E T E C T O R S
MASTER
S L A V E D E T E C T O R
TM
S L A V E D E T E C T O R
TM
Master 1
Local = y
Remote = n
Slave loop
Reference
Slave
H I G H S E N S I T I V I T Y S M O K E D E T E C T O R
TM
ISOLATE
TEST
RESET
S M O K E D E N S I T Y
AUX
FIRE
PRE-
ALARM
RENEW
OK
FAULT
OK
ISOL.
ON
FAULT
OK
HIGH
OK
LOW
1
2
3
4
Ref.
Air Flow
1
2
3
4
5
6
7
8
9
10
Detector
Power
Separator
Artificial Intelligence
With
S L A V E D E T E C T O R S
MASTER
S L A V E D E T E C T O R
TM
S L A V E D E T E C T O R
TM
Master 2
Local = y
Remote = n
Slave loop
Reference
Slave
H I G H S E N S I T I V I T Y S M O K E D E T E C T O R
TM
ISOLATE
TEST
RESET
S M O K E D E N S I T Y
AUX
FIRE
PRE-
ALARM
RENEW
OK
FAULT
OK
ISOL.
ON
FAULT
OK
HIGH
OK
LOW
1
2
3
4
Ref.
Air Flow
1
2
3
4
5
6
7
8
9
10
Detector
Power
Separator
Artificial Intelligence
With
S L A V E D E T E C T O R S
MASTER
S L A V E D E T E C T O R
TM
S L A V E D E T E C T O R
TM
Master 1
Local = y
Remote = n
Slave loop
Tx/GND
Rx/GND
Reference output
Additional
Masters
Reference
Slave
H I G H S E N S I T I V I T Y S M O K E D E T E C T O R
TM
ISOLATE
TEST
RESET
S M O K E D E N S I T Y
AUX
FIRE
PRE-
ALARM
RENEW
OK
FAULT
OK
ISOL.
ON
FAULT
OK
HIGH
OK
LOW
1
2
3
4
Ref.
Air Flow
1
2
3
4
5
6
7
8
9
10
Detector
Power
Separator
Artificial Intelligence
With
S L A V E D E T E C T O R S
MASTER
S L A V E D E T E C T O R
TM
Master 2
Local = y
Remote = n
Slave loop
Slave