6
ELECTRICAL REQUIREMENTS
NOMINAL VOLTAGE LEVEL
The Nominal AC Line Voltage requirements for your system are 3-Phase 230 VAC ± 5%, phase balance ± 3%,
and a 20 Amp circuit. Operation of your system outside this range, even for short periods, is not recommended,
as it will result in degraded system performance and component life expectancy. The ideal output voltage from
the transformer is 230 VAC to 235 VAC.
POWER QUALITY
AC power quality is key to reliable performance. The 360mc/400mc system is a precision tool that requires good
power quality. Its design incorporates a number of power quality control measures. Customers are required to
meet the power quality and nominal voltage requirements.
AC power should be provided to the system with a dedicated 3-phase feed. Recommendations of power quality
are given in IEEE Standard 141-1976 and FIPS PUB 94. Customers which are unsure of their power quality
need to contact their provider.
ELECTRICAL REQUIREMENTS - JA 100 EXTERNAL AIR COMPRESSOR
The optional external air compressor requires dedicated 50/60HZ, 230 VAC, Single Phase, 15 Amp, electrical
service. The air compressor includes an 8 ft. (2.5m) power cable requiring the installation of an AC service
connector.
TRANSFORMER - JA 100 EXTERNAL AIR COMPRESSOR (NORTH AMERICA
ONLY)
A proven transformer solution for use with the JA-100 External Air Compressor.
Stratasys Part Number
Manufacturer
Incoming Service Voltage
600-00100
Badger Magnetics
200/208/220/240V WYE, 3 phase
600-00200
Badger Magnetics
380/400/415/440V WYE, 3 phase
600-00400
Badger Magnetics
480V WYE, 3 phase
Voltage
Frequency
Max Current
230VAC
50Hz
6.8 Amps
230VAC
60Hz
8.2 Amps
Manufacturer
Part Number
Description
Contact
Federal Pacific
SB16N.250F
General purpose transformer, single
phase, 600 volt class, 60 Hz.
Transformer is wall mounted and is
light gray in color.
Midwest Machine Tool Supply
1.800.327.9523