background image

 

 

H71 

 

Sunday ON1 

H72 

 

Sunday OFF1 

H73 

 

Sunday ON2 

H74 

 

Sunday OFF2 

H75 

 

Sunday ON3 

H76 

 

Sunday OFF3 

 
H0 

 

0: switching times not activated  

  

 

1: switching times activated 

 
By pressing the SET TIME key the respective time is indicated and can be adjusted by pressing 
the UP or DOWN key in addition. After releasing all key the new value is saved.  
With parameter H0 the timer can be switched off without changing the switching times. 
 
Adjustment notes: 
The programming takes place by analogy with a mechanical timer where a mark can (but not has 
to) be set for switch on and switch off timers. The infinite loop of the programming cycle permits a 
quick access to the parameters for Saturday and Sunday by pressing the DOWN key.  
 
Note that no switching takes place if the adjusted switch-on and switch-off time of an output is the 
same on the same day. A overlapping of the time values is possible but the respective switching 
time couple becomes ineffective.  
 
Between “23:59” and “00:00” the switching times have the special position “----“.  With this setting 
the respective switching time is deactivated and has no more effect on the switching condition of 
the respective output. This is used to have outputs switched on until next day for example. 
 
If in the programming cycle the SET TIME key and the PROG key are pressed at the same time, 
all times of the day before are copied to the selected day and the display indicates “CPY”. Note 
that the key SET TIME has to be pressed first and after that the PROG key. 
 
 
Leaving programming cycle: 
The programming cycle is leaved if the PROG key is pressed again for 3 seconds or if no key is 
pressed for min. 60 seconds.  
 
 

Содержание 900219.005

Страница 1: ...on of a temperature controller which can be switched on and or off with the integrated week timer Daily the programming cycle can be pre set with three switch on and off times The programming cycle runs through all set positions in a continuous loop The display indicates the current selection Measurement range dependent on type of sensor Front size 106mm x 68mm Panel cut out 87 5mm x 56 5mm Connec...

Страница 2: ......

Страница 3: ... the PROG key in addition Key PROG If this key is pressed for 3 seconds the programming cycle of the switching times is accessed always starting with parameter H0 Within the programming cycle the time settings of the previous day can be copied to the selected day by additionally pressing the SET TIME key While doing so the SET TIME key is to be pressed first and than the PROG key in addition The d...

Страница 4: ...w value is saved To adjust the weekday you have to adjust the time further than midnight Parameter setting of the control setpoint Pressing the UP or DOWN key for 3 seconds the setpoint shows on the display and can be adjusted with the keys UP and DOWN The setpoint is stored if none of the keys is pressed for 3 seconds Para meter Function description Adjustment range Standard setting Custom settin...

Страница 5: ...ON2 H14 Monday OFF2 H15 Monday ON3 H16 Monday OFF3 H21 Tuesday ON1 H22 Tuesday OFF1 H23 Tuesday ON2 H24 Tuesday OFF2 H25 Tuesday ON3 H26 Tuesday OFF3 H31 Wednesday ON1 H32 Wednesday OFF1 H33 Wednesday ON2 H34 Wednesday OFF2 H35 Wednesday ON3 H36 Wednesday OFF3 H41 Thursday ON1 H42 Thursday OFF1 H43 Thursday ON2 H44 Thursday OFF2 H45 Thursday ON3 H46 Thursday OFF3 H51 Friday ON1 H52 Friday OFF1 H53...

Страница 6: ... that no switching takes place if the adjusted switch on and switch off time of an output is the same on the same day A overlapping of the time values is possible but the respective switching time couple becomes ineffective Between 23 59 and 00 00 the switching times have the special position With this setting the respective switching time is deactivated and has no more effect on the switching con...

Страница 7: ... can be adjusted Return to the initial position takes place automatically if no key is pressed for 60 seconds Para meter Function description Adjustment range Standard setting Custom setting P0 Actual value P2 Hysteresis contact K1 0 1 99 9 K 1 0 K P4 Control range limitation minimum setpoint 99 C P5 99 C P5 Control range limitation maximum setpoint P4 999 C 999 C P6 Actual value correction 20 0 2...

Страница 8: ...r of a unit from setting inadmissible or dangerous setpoints P6 Actual value correction This parameter allows the correction of actual value deviations caused for example by sensor tolerances or extremely long sensor lines The regulation measure value is increased or decreased by the here adjusted value P19 Key lock The key lock allows blocking of the control keys In locked condition parameter adj...

Страница 9: ...g contact 1 cooling contact 0 A3 Function of contact K1 at sensor error 0 relay off 1 relay on 0 A8 Display mode all parameter indications are presented in 0 1 K 0 integrals 1 decimals in 0 5 C 2 decimals in 0 1 C 1 A19 Parameter lock 0 no lock 1 A parameter locked 2 A and P parameter locked 0 A30 Function alarm exit 0 Boundary alarm relative 1 Boundary alarm absolute 2 Range alarm relative 3 Rang...

Страница 10: ...0 two wire 21 PTC 22 PT1000 two wire 21 A70 Software filter 1 inactive Average value with 2 2 measuring values 4 4 measuring values 8 8 measuring values 16 16 measuring values 32 32 measuring values 64 64 measuring values 4 A80 Temperature scale 0 Fahrenheit 1 Celsius 1 A87 Function key Standby 0 no function 1 controller On Off Standby 1 Pro Program version ...

Страница 11: ...in these two limits or whether the alarm is released if the temperature lies beyond them In the case of sensor error the alarm is activated independently of this adjustment The exit can also be inverted so that it functions like a release A31 Special function at boundary or range alarm Here can be selected whether in the case of an alarm the indication to flash and or the buzzer is to start Sensor...

Страница 12: ...e if the needed hardware prerequisites are available A70 Software filter With several measuring values it is possible to obtain an average value This parameter can determine by how many measured values an average value is to be formed If a sensor with a very fast reaction to external influences is used an average value ensures a calm signal process A80 Temperature scale Indication can be switched ...

Страница 13: ...circuit at sensor F1 Check sensor _ _ _ Key lock active Change parameter P19 or A19 display flashes Temperature alarm at too high or too low temperature if activated see A31 rC Data loss in real time clock chip Setting the clock rF Real time clock chip fault Controller must be repaired EP Data loss at parameter memory Controller must be repaired ...

Страница 14: ...1 are on LED3 Key All On is activated see key description Power supply 12 24 V AC 50 60 Hz or 16 36V DC Ambient conditions Storage temperature 20 70 C Operating temperature 0 55 C Relative Humidity max 75 without dew Weight ca 160g Connectors Screw terminal 7 pole spacing 5mm for cable up to 1 5mm Screw terminal 2 pole spacing 5mm for cable up to 1 5mm Internal battery Lithium battery 3 V for buff...

Отзывы: