background image

 

Order No.: 900220.020 

V2.24 

7/11

 

Parameter description: 

 

The following values can change the equipment characteristics 

and are therefore to be set with utmost care. 

 

P0: Indication actual value of sensor F1 

The here indicated temperature presents the sum of 
actual measured value of feeler F1 and the actual 
value correction according to parameter P1. 
 

P1: Calibration sensor F1, actual value 
correction

 

This parameter allows the correction of actual value 
deviations caused for example by sensor tolerances 
or extremely long sensor lines. The regulation 
measure value is increased or decreased by the 
here adjusted value. 
 

P2: Indication actual value of sensor F2 

The here indicated temperature presents the sum of 
actual measured value of sensor F2 and the actual 
value correction according parameter P3. 
 

P3: Calibration sensor F2, actual value 
correction 

This parameter allows the correction of actual value 
deviations caused for example by sensor tolerances 
or extremely long sensor lines. The regulation 
measure value is increased or decreased by the 
here adjusted value. 
 

P4: Evaluation of sensor F2 

Sensor F2 can be used for the determination of the 
evaporator temperature (P4=1) or for the second 
thermostat (P4=2). 
If, in simpler refrigerant plants only the refrigerating 
chamber sensor is used, the feeler entrance for 
sensor F2 as well as its data recording (P4=0) can 
be deactivated here. Among other, parameter d2 
has no meaning in the deactivated condition. 
 

P5: Indication mode 

The actual value can be indicated with different 
accuracy. 
Actual values and parameter values are always set 
for highest accuracy. 
 

P6: Display unit, indication in standby mode 

This parameter allows display settings (°F or °C) and 
("AUS" or "OFF") in standby mode. 
 

P7: Sensor type 

This parameter makes it is possible to adjust the 
feeler type of both sensors. Depending on the 
hardware not all sensor settings are possible. 
 

P8: Filter 

This parameter can determine by how many 
measured values an average value is to be formed. 
 

r0: Hysteresis for the compressor contact 

Parameter r0 sets the temperature margin between 
switching off and switching on of the compressor. A 
small hysteresis permits a more exact regulation, 
however also leads to more frequent switching of the 
compressor. The hysteresis is set one-sided above 
the setpoint.  
 

r1: Setpoint limitation (minimum) 
r2: Setpoint limitation (maximum) 

These parameters limit the adjustment range of the 
setpoint S1, in order to avoid that the end user sets 
inadmissible values for the plant. 
The entire adjustment range is equivalent to the 
maximum operating range of a PTC sensor. 
 

r3: Switching sense of the compressor 

 

c0: Start protection of the compressor after 
"cooling on" 

After cooling is switched on (e.g. by switching on the 
mains voltage) the start of the compressor is 
retarded until the protection running time is over. 
This secures e.g. that several cooling units do not 
start at the same time and load the electricity supply 
net.  
 

c1: Start protection of the compressor after 
compressor start 

This time protection starts when the compressor is 
switched on. After switching the compressor off, a 
renewed switching on is impossible until this 
protection time runs out. This prevents from too 
frequent switching-on of the compressor and thus 
increases its life span. 
 

c2: Start protection of the compressor after 
compressor stop 

This time protection starts when the compressor is 
switched off. After switching the compressor off, a 
renewed switching on is impossible until this 
protection time runs out. 
 

c3: Function in the case of error of refrigerating 
chamber sensor F1 

Here is determined whether the compressor keeps 
running or not in the case of an error of the 
refrigerating chamber feeler F1. When deep-
freezing, the compressor should normally continue 
running, in order to prevent de-frosting of the goods. 
At the normal cooling range above 0 °C, a 
continuation, however, could lead to frost damages. 
In the operation mode "emergency operation" the 
compressor is switched on and off in 5 minute 
intervals. This results in a clock operation with 50 % 

Содержание ST501-KU3KA.12P

Страница 1: ...t is supplied with 230V AC and has four relay outputs as well as an exit for a DC voltage fan The relays can be used for different functions e g for a compressor a defroster an alarm relay etc see parameters U1 U4 The two resistance sensors seize the refrigerating chamber temperature and the evaporator temperature Sensor PTC Range 55 99_C Front size 106mm x 68mm Panel cut out 87 5mm x 56 5mm Tight...

Страница 2: ...Order No 900220 020 V2 24 2 11 ...

Страница 3: ...n addition the SET key is used for setting parameters Key 6 Standby With this key the controller is switched to standby mode Pressing the key a second time restarts the unit The key can be deactivated by setting the respective parameter see parameter b3 First control level Parameter setting for the main setpoint If none of the keys is pressed the display indicates the actual value of the temperatu...

Страница 4: ...s Access to the third control level is granted when selecting parameter PA on the second control level Parameter PA is to be set at 19 Then the key UP and DOWN have to be simultaneously pressed for approx 4 seconds which will give access to the third control level beginning with parameter P0 With the keys UP and DOWN you can scroll the list in both directions Pressing the SET key will give you the...

Страница 5: ... 150 C 10 C 5 0 C d3 Defrosting time limit 1 99 min 30 min 20 min d6 Indication of the refrigerating chamber temperature during defrosting 0 actual temperature 1 temperature determined just before the start of defrosting 1 d7 Drainage time 0 15 min 2 min 0 min A0 Hysteresis for alarm 1 15 K 2 K 5 K A1 Minimum limit value 99 0 0 1 K 0 inactive 10 K A2 Maximum limit value 0 1 99 0 K 0 inactive 10 K ...

Страница 6: ...y switched off in standby mode 4 relay directly regardless of standby mode 0 b12 Function switching input E2 see b11 0 b13 Function switching input E3 if available see b11 0 b14 Function switching input E4 if available see b11 0 U1 Exit connection K1 0 no connection 1 connection to compressor 2 connection to defrost 3 connection to ventilator 4 connection to alarm 5 connection to thermostat 2 6 co...

Страница 7: ...y how many measured values an average value is to be formed r0 Hysteresis for the compressor contact Parameter r0 sets the temperature margin between switching off and switching on of the compressor A small hysteresis permits a more exact regulation however also leads to more frequent switching of the compressor The hysteresis is set one sided above the setpoint r1 Setpoint limitation minimum r2 S...

Страница 8: ...ysteresis for alarm The hysteresis of the alarm contact is asymmetrically set downward at the maximum alarm value upward at the minimum alarm value A1 A2 Minimum maximum limit values The limit values serve for monitoring of the refrigerating chamber temperature They are relative i e going along with the setpoint S1 of the refrigerating chamber Alarm is released when exceeding maximum limit value o...

Страница 9: ...key is pressed again or until it is changed by an external switching entrance After net interruption the condition before power failure is re installed At setting 5 the actual value of sensor 2 can be indicated At setting P4 0 the key has no function b3 Function key 3 standby At setting b3 0 the function of the key can be deactivated b11 Function external entrance E1 b12 Function external entrance...

Страница 10: ...c3 1 the controller operates in timed defrosting modus defrosting time as set in d3 At setting c3 2 see parameter Y6 EP Data loss at parameter memory basic contact 1 and 2 are dead If error cannot be eliminated by switching on off the controller must be repaired Error message E0 E1 and EP changes in the display with the actual value of sensor F1 unless the latter is defective This happens independ...

Страница 11: ... A 250V normally open contact function see U3 K4 Relay 16 2 2 A 250V normally open contact fan voltage output for DC fan 0 24V max 800mA corresponds 20W Display One 3 digit LED Display height 13 mm for temperature indication Three LEDs diameter 3mm for status display of the outputs Power supply 230V 50 60Hz power consumption max 40 VA Connectors Cage clamp 5 x 3 pole for cable up to 2 5mm Cage cla...

Отзывы: