Order No.: 900220.020
V2.24
6/11
Para-
meter
Function
Adjustment range
Standard
setting
Customer
setting
b1
Function key A
(if available)
0: no function
1: controller on/off (standby)
2: Setpoint thermostat 2 (Y1)
3: relay directly, switched off in
standby mode
4: relay directly, regardless of
standby mode
5: actual value sensor F2 (toggle)
0
4
b2
Function key B
(if available)
see b1
0
b3
Function standby key
0: no function
1: controller on/off (standby)
1
b11
Function switching input E1
0: no function
1: controller on/off (standby)
2: starting defrost
3: relay directly, switched off in
standby mode
4: relay directly, regardless of
standby mode
0
b12
Function switching input E2
see b11
0
b13
Function switching input E3
(if available)
see b11
0
b14
Function switching input E4
(if available)
see b11
0
U1
Exit connection K1
0: no connection
1: connection to compressor
2: connection to defrost
3: connection to ventilator
4: connection to alarm
5: connection to thermostat 2
6: connection to key A, E1 or E3
7: connection to key B, E2 or E4
8: connection to buzzer
9: on, if controller on
1
U2
Exit connection K2
see U1
2
U3
Exit connection K3
(if available)
see U1
3
6
U4
Exit connection K4
(if available)
see U1
4
L0
Own ST-Bus address
0: inactive
1 ... 250
0
L40
Mask for Low-Byte of Status 0
(ST-Bus)
0 ... 255 (binary coded)
Pro
Program version