Second control level (P-parameters):
Adjustment of control parameters
The one-finger-setup of the setpoint adjustment requires an exactly simultaneous pressing of the
UP and DOWN key for at least 4 seconds to open a parameter list containing control parameters.
(If by mistake the setpoint adjustment is released a new attempt is possible after 5 seconds.)
With the UP and DOWN keys the list can be scrolled in both directions.
Pressing key 3 will give you the value of the respective parameter. Pressing also the UP or DOWN
key at the same time the value can be adjusted.
Return to the initial position takes place automatically if no key is pressed for 60 seconds.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
P1
Setpoint 2 or
DeltaW
-99.9...999°C
-99.9...99.9 K
0.0 °C
P2
Hysteresis contact K1
1...99 K
1.0 K
P3
Hysteresis contact K2
1...99 K
1.0 K
P4
Control range limitation – minimum
setpoint
-99.9...P5°C
0.0°C
P5
Control range limitation – maximum
setpoint
P4...999.9°C
205 °C
P7
Proportional band
1...100 K
10.0 K
P8
Reset time Tn (I-factor)
0...999 sec.
(0 sec. = inactive)
0 sec.
P9
Lead time Tv (D-factor)
0...999 sec.
(0 sec. = inactive)
0 sec.
P10*
Cycle time Tp
2...100 sec.
10 sec.
P19
Key-lock
(only for setpoint setting)
0: no key-lock
1: key-lock
0
P20
Indication of actual value sensor F1 -----
-----
P21
Actual value correction sensor F1
-20...20.0 K
0.0 K
P24
Switch off delay
Control contact 1
0.0...99.0 sec.
0.0 sec.
P25
Temperature limit for fat operating
time
0.0...999 °C
999 °C
P26
Fat operating time until fat alarm
message
0...99 h
(0 h = inactive)
0 h
P27
Fat operating time until regulation
blocking
0...99 h
(0 Std. = inactive)
0 h
P28
Indication of fat operating time
-----
-----
P29
Temperature limit for reset of fat
operating times
-99...999 °C
100 °C
P30
Lower alarm value
-99,9°C/K...P31
-40 °C
P31
Upper alarm value
P30...999 °C/K
208 °C
P32
Hysteresis alarm circuit
0,1...99.9 K
1.0 K
P35
“Reduced heating” – heating on
1...255 sec.
60 sec.
P36
“Reduced heating” – heating off
1...255 sec.
90 sec.
P37
End of “reduced heating” below
setpoint
-99...0.0 K
-30 K
* The PID-control suppressed switch-on times below 0.1 seconds.