background image

 

 

Adjustment options

 

 

Key 1: UP 

Pressing this key you can increase the parameter or parameter value or scroll the 
parameter list. 
 
 

Key 2: DOWN 

Pressing this key you can decrease the parameter or parameter value or scroll the 
parameter list. At alarm the buzzer function can be switched off with this key. Any fat 
alarm message can be switched off as well, however the internal alarm condition 
remains active and the alarm restarts at each unit start. 
 

Key 3: selection of temperature setpoint 

With this key the temperature setpoint relevant for the regulation is selected. If 
previously the timer display is active the controller at first switches to temperature 
display with the first key pressing. With parameters you can determine if the respective 
setpoint is still selected after switching of the mains voltage or if one of the setpoints 
S1-S3 is selected. 
 

Key 4: selection of timer setpoint 

With this key the timer setpoint is selected and the LED of the timer lights up. The value 
shows up in the display for 5 seconds and can be adjusted with the UP and DOWN key. 
If none f the key is pressed the display automatically shows the temperature again, the 
timer LED goes out. If the key is pressed for 2 seconds the timer is started and the LED 
flashes. The remaining time is shown only for a moment but the flashing LED indicates 
the elapsing timer. A permanent display of the remaining time can be activated with 
parameters, then the LED of the timer is permanently on. If the key is pressed for 5 
seconds the timer is stopped and the display indicated “0:00”. 
 

Key 3+4: setpoint reduction 

Simultaneously pressing these two keys activates the setpoint reduction, in addition 
with the UP and DOWN key it can be adjusted. Please note that the setpoint reduction 
is only effective in case of a closed switching input. In case of an activated setpoint 
reduction a point flashes no the right side of the display. Setpoint reduction is only 
possible with controllers with switching input(s). 
 

Key

 

5: MELT/TURBO 

With this toggle key one can choose between reduced and accelerated heating mode. 
Together with the thermostatic function the turbo-heating offers a further increase of 
heat supply. After switching on the controller the turbo-heating always is deactivated. 
The key is ineffective if the reduced heating mode is deactivated or in some 
temperature ranges if no PID characteristic is selected. See below for all choice 
options. 
 

Key 6: ON/OFF

 

If this key is pressed for 1 second the controller switches to standby mode, the display 
shows “OFF” or “AUS” and a started timer cycle is aborted. After switching mains on the 
controller always is in standby mode. The key can be deactivated, then the controller is 
switched on with mains voltage. 
 

Содержание 900219.092

Страница 1: ...ller and is cut to the use with deep fryers It has a 4 digit LED display 6 keys 2 relays and a switching input The different temperature setpoints and timer defaults can be parametered directly by the keys Sensor multi resistance input Range dependent on the type of sensor Front size 106mm x 68mm Panel cut out 87 5mm x 56 5mm Tightness front IP64 Connector screw terminal ...

Страница 2: ......

Страница 3: ...ivated with parameters The output relays are two change over contacts The functions heating control contact 2 or alarm can be assigned to each output even the deactivation of a output is possible The controller has the possibility of a particularly careful heating in case the deep fryer fat is not yet melted This retarded heating process Melt function is always activated after switching no the uni...

Страница 4: ...ing time is shown only for a moment but the flashing LED indicates the elapsing timer A permanent display of the remaining time can be activated with parameters then the LED of the timer is permanently on If the key is pressed for 5 seconds the timer is stopped and the display indicated 0 00 Key 3 4 setpoint reduction Simultaneously pressing these two keys activates the setpoint reduction in addit...

Страница 5: ...e OIL is deleted and if necessary the regulation blocking is cancelled The accumulated operating time is deleted Note that a reset is only possible in case of an alarm message or blocking and below the adjusted temperature limit value This is to prevent the user from operating the deep fryers without replacing the fat However an unconditional reset can be enabled by means of parameters ...

Страница 6: ...ing PID Turbo was possible the key now is ineffective 3 A6 1 A88 0 The melt function is deactivated and the PID control activated The controller has no reduced heating phase below the limit P37 In each case where switching Melt Turbo was possible it is now possible to switch between PID Turbo 4 A6 0 A88 0 Both the melt function and the PID control are deactivated The controller has no reduced heat...

Страница 7: ...ndicated by pressing keys 3 4 together By additionally pressing the UP or DOWN key it can be adjusted Para meter Function description Adjustment range Standard setting Custom setting S1 S2 S3 Temperature setpoints the currently selected setpoint is indicated and or adjusted P4 P5 C 170 C 160 C 100 C T1 Timer setpoint 0 00 99 99 Min 1 11 Min S1 Setpoint reduction is added to the main setpoint in ca...

Страница 8: ...0 C P5 Control range limitation maximum setpoint P4 999 9 C 205 C P7 Proportional band 1 100 K 10 0 K P8 Reset time Tn I factor 0 999 sec 0 sec inactive 0 sec P9 Lead time Tv D factor 0 999 sec 0 sec inactive 0 sec P10 Cycle time Tp 2 100 sec 10 sec P19 Key lock only for setpoint setting 0 no key lock 1 key lock 0 P20 Indication of actual value sensor F1 P21 Actual value correction sensor F1 20 20...

Страница 9: ... 2 Cooling controller symmetrical hysteresis The hysteresis is only effective if thermostatic mode is enabled in case of PID characteristic it is ineffective P4 Control range limitation minimum setpoint P5 Control range limitation maximum setpoint The adjustment range of the setpoint can be limited in both directions This is to prevent the end user of a unit from setting inadmissible or dangerous ...

Страница 10: ...ure limit for fat operating time Above this temperature the internal recording of fat operating time is started If the values of P26 and P27 are exceeded the alarm message and or regulation blocking is activated P26 Fat operating time until fat alarm message After this time period an alarm message requests the exchange of the deep frying fat The display indicates flashing OIL With P26 0 this funct...

Страница 11: ... boundary value Fig 5 Boundary alarm rel boundaries Range alarm function see fig 6 Opposite switching behaviour to the boundary value alarm The alarm contact is closed if the actual value remains between the boundary values Fig 6 Range alarm abs boundaries P32 Hysteresis alarm contact The hysteresis can be set symmetrically or one sided at the adjusted limit values see A42 It becomes effective dep...

Страница 12: ...1 cooling contact 0 A2 Switch mode contact K2 0 heating contact 1 cooling contact 0 A3 Function of contact K1 at sensor error 0 relay off 1 relay on 0 A4 Function of contact K2 at sensor error 0 relay off 1 relay on 0 A5 Selection setpoint 2 or DeltaW 0 operation with setpoint 2 1 operation with DeltaW 0 A6 Control characteristics contact K1 0 thermostatic 1 PID 0 A8 Display mode 0 integrals 1 res...

Страница 13: ...ff 0 0 99 0 sec 0 0 sec A56 Alarm suppression after mains on standby on 0 60 min 0 min A60 Sensor type 11 Pt100 2 wire 21 PTC 22 Pt1000 2 wire 11 A70 Software filter 1 not active or else 2 32 average value with 2 32 measuring values 2 A80 Temperature scale 0 Fahrenheit AUS 1 Celsius AUS 2 Fahrenheit OFF 3 Celsius OFF 3 A85 Reset mode of fat operation time 0 reset after alarm message or blocking an...

Страница 14: ...ontact K1 at sensor error A4 Function of contact K2 at sensor error At sensor error the selected relay falls back into the condition pre set here If there is a data loss in parameter memory display indicates EP both contacts K1 and K2 are switched off A5 Selection setpoint 2 or DeltaW This parameter determines whether the setpoints for thermostat 1 and 2 independently adjustable A5 0 or whether th...

Страница 15: ...e temperature lies beyond them In the case of sensor error the alarm is activated independently of this adjustment The output can be inverted to operate as a release A31 Special function at boundary or alarm Here can be selected whether in the case of an alarm the indication to flash and or the buzzer is to start Sensor alarm display F1L or F1H is indicated independently thereof by flashing displa...

Страница 16: ... This parameter can determine by how many measured values an average value is to be formed If a sensor with a very fast reaction to external influences is used an average value ensures a calm signal course A80 Temperature scale Indication can be switched between Fahrenheit and Celsius At conversion the parameters and setpoints maintain their numerical value and adjustment range Example A controlle...

Страница 17: ...eliminated by resetting the unit the controller must be repaired OIL flashing regulation runs Alarm message caused by fat operation time exceeding see P26 Delete with DWON key OIL flashing regulation blocked Regulation blocking caused by fat operation time exceeding see P27 Delete with MELT ON OFF key rES Confirmation of the reset of the fat operating time Key lock see P19 and or A19 Flashing disp...

Страница 18: ...r PTC Pt100 Measuring range PTC KTY81 121 50 C 130 C Pt100 80 C 400 C Accuracy 0 5K 0 5 at 25 C without sensor 1K 0 5 of scale range 0 55 C without sensor Outputs K1 Relay 10 1 5 A 250V change over contact K2 Relay 8 1 5 A 250V change over contact Summer ca 85dB Display One 4 digit LED Display height 13 mm colour red 6 LEDs for status display Power supply 230 V 50 60 Hz power consumption max 6 VA ...

Отзывы: