Parameter description: 

 

The following values may change the equipment 

characteristics and are therefore to be set with the utmost care: 

 

A1: Fan controller mode 
A2: Control circuit 2 mode 

The controller mode (cooling or heating function) can be individually programmed for the two 
control circuits at the factory. Heating function means that the contact drops out when the defined 
setpoint is reached, i.e. the power supply is interrupted. In the case of the cooling function, the 
contact only picks up when the actual value is above the defined setpoint. 
 

A3: Fan controller function in the event of a sensor error 
A4: Control circuit 2 function in the event of a sensor error 

When the sensor is broken, the flashing display indicates F1H. When the sensor is short-circuited, 
the display indicates F1L (also flashing). Parameter A3 is used to determine the output behavior 
when this happens 
 

A5: Selection of setpoint 2 / delta W for control circuit 2 

This parameter determines whether the controller works with two linked contacts (operation with 
delta W) or with two independently adjustable contacts (operation with setpoint 2). See P1. 
 

A8: Display mode 

This parameter selects the resolution used to display the actual value. 

 
A19: Parameter lock 

This parameter can be used to lock (block access to) the parameter levels. When the A level is 
locked, only parameter A19 can still be changed. 
When the parameter lock is active, the parameters are displayed but cannot be changed via the 
keys. Any attempt to change parameters with keypad locking enabled will display the message 
“---“. 
 

A30: Alarm contact function 

This parameter is used to determine alarm contact behavior when the values set with parameters 
P30 and P31 are reached. 
Limit alarm means that an alarm is signaled when the defined limits are exceeded. 
Range alarm means that an alarm is signaled within the defined limits. 
Relative means that the values entered for parameters P30 and P31 represent a difference from 
the setpoint. Absolute means that the values entered for parameters P30 and P31 are independent 
of the setpoint. 
 

A31: Special limit alarm function 

This parameter can be used to activate additional actions for the limit alarm function. 

 

A32: Default display setting 

When parameter A32 is set to 1, the display always indicates the setpoint. It is then not possible to 
display the actual value. 
 

A40 Hysteresis mode of fan controller 
A41 Hysteresis mode of control circuit 2 

These parameters determine whether the hysteresis values adjusted with P2 or P3 for the fan 
controller or control circuit 2 are symmetrical or one-sided relative to the switching point in 
question. When the symmetrical hysteresis function is chosen, half of the hysteresis value is 
effective above and half of the value below the switching point. When the one-sided setting is 
chosen, the hysteresis works downward with the heating contact and upward with the cooling 
contact. 

Содержание 149674

Страница 1: ...s are established in the rear on the power supply unit board The unit provides the functionality of a temperature controller for fan drawers A triac for fan control and a relay are provided as outputs The relay is a normally open contact and can be defined either as control circuit 2 or as an alarm contact using the parameter setting function Sensor PTC Pt100 Range dependent on type of sensor Fron...

Страница 2: ......

Страница 3: ...y is pressed This key is also used to set parameter values Standby key This key switches the controller to the standby mode Press the key again to switch the controller back on First control level Parametrization of primary setpoint The actual value is always shown on the setpoint display Press the SET key to display the setpoint setting Additionally press the UP key or DOWN key to adjust the valu...

Страница 4: ...ult setting Custom setting P0 Displays the actual value from sensor F1 P1 Setpoint 2 delta W Control circuit 2 P4 P5 99 99 K Delta W 10 K P2 Hysteresis control circuit 1 0 1 99 9 K 1 0 K P3 Hysteresis control circuit 2 0 1 99 9 K 1 0 K P4 Lower control range limit 99 C P5 99 C P5 Upper control range limit P4 999 C 999 C P6 Actual value correction 20 20 K 0 0 K P7 Proportional band 0 1 100 K 10 0 K...

Страница 5: ...steresis K1 K2 The hysteresis may be symmetrical or one sided relative to the setpoint see A40 A41 When the one sided setting is chosen the hysteresis works downward with the heating contact and upward with the cooling contact When the symmetrical hysteresis function is chosen half of the hysteresis value is effective above and half of the value below the switching point cf figures 3 and 4 Figure ...

Страница 6: ...e case of very fast processes with high switching frequencies a voltage output is therefore preferable P19 Keypad locking The keypad locking function can be used to block the control keys When keypad locking is enabled the setpoint cannot be changed Any attempt to change parameters with keypad locking enabled will display the message P30 Lower alarm limit P31 Upper alarm limit A limit or range ala...

Страница 7: ...ontrol level which starts with A1 Press the UP key to scroll up in the list and the DOWN key to scroll down in the list Press the SET key to display the value of the parameter in question To adjust the value additionally press the UP key or DOWN key Once you release all keys the new value is permanently stored If no key is pressed for more than 60 seconds the unit automatically returns to its init...

Страница 8: ...eresis mode of control circuit 2 0 symm around setpoint 1 on one side of setpoint 0 A52 Minimum action time control circuit 2 on 0 600 sec 0 sec A53 Minimum action time control circuit 2 off 0 600 sec 0 sec A54 Delay after power on 0 600 sec 20 sec A56 Alarm suppression of limit alarm after power on 0 60 min 0 min A57 Continuous fan operation outside proportional band with value from P33 0 no cont...

Страница 9: ...9 can still be changed When the parameter lock is active the parameters are displayed but cannot be changed via the keys Any attempt to change parameters with keypad locking enabled will display the message A30 Alarm contact function This parameter is used to determine alarm contact behavior when the values set with parameters P30 and P31 are reached Limit alarm means that an alarm is signaled whe...

Страница 10: ...ormally result in undesirable alarm signaling Therefore parameter A56 can be used to define a period of time during which an alarm condition is not signaled A57 Continuous fan operation A60 Sensor selection Selection of sensor Depending on the hardware used not all sensor types can be selected A70 Software filter Calculates the mean value over the number of measurements set here A 80 Temperature s...

Страница 11: ...1 triac output for fan Additional buzzer 85 dB Display and indicators One 3 digit LED display for temperature indication Three LEDs for status indication Power supply 230 V 50 60 Hz Connectors 12 pin screw terminal 5 0 mm pitch for cable cross sections of up to 2 5 mm Weight Approx 250 g without sensor Type of protection Front IP65 Ambient conditions Storage temperature 20 C 70 C Operating tempera...

Отзывы: