Param-
eter
Function description
Adjustment range
Default
setting
Custom
setting
A30
Alarm contact function
0: limit alarm, relative
1: limit alarm, absolute
2: range alarm, relative
3: range alarm, absolute
4: limit alarm, relative
inverted alarm contact
5: limit alarm, absolute
inverted alarm contact
6: range alarm, relative
inverted alarm contact
7: range alarm, absolute
inverted alarm contact
1
A31
Special functions for alarm
0: no special function
1: flashing display
1
A32
Default display setting
0: actual value display
1: setpoint display
0
A40
Hysteresis mode of fan
controller
0: symm. around setpoint
1: on one side of setpoint
0
A41
Hysteresis mode of control
circuit 2
0: symm. around setpoint
1: on one side of setpoint
0
A52
Minimum action time
control circuit 2 “on“
0 … 600 sec.
0 sec.
A53
Minimum action time
control circuit 2 “off“
0 … 600 sec.
0 sec.
A54
Delay after “power on“
0 … 600 sec.
20 sec.
A56
Alarm suppression of limit
alarm after “power on“
0 … 60 min.
0 min.
A57
Continuous fan operation
(outside proportional band
with value from P33)
0: no continuous operation
1: continuous operation
1
A60
Sensor selection
11: Pt100 two-wire
21: PTC
22: Pt1000 two-wire
21
A70
Software filter
1: not active, otherwise
2 ... 32: mean value of 2...32
meas. values (approx.
0.6...9.6 s)
4
A 80
Temperature scale and
display
0: Fahrenheit (AUS)
1: Celsius (AUS)
2: Fahrenheit (OFF)
3: Celsius (OFF)
1
A90
K1 output linking
0: no linking
1: linked with
control circuit 2
2: linked with
alarm contact
1
Pro
Program version display
-----
-----
-----