StoneL Axiom AN Скачать руководство пользователя страница 23

StoneL publication 105410revD

7 AN 70  en

Axiom AN | 

23

5.4 

Device detail screen

You can customize the tag for a device, change the address, change 
the baud rate (if applicable), force the solenoids on or off, cause the 
device to wink, and set the open/closed limits from the device detail 
screen (Image 4a or 4b).

Image 4a - DeviceNet detail

Image 4b - ASi detail

E

M

K

L

J

I

G

F

N

H

Changing the device tag or address on a DeviceNet unit

1.  To change the tag, edit the existing tag in the associated text field 

(Item E). The tag can be up to sixteen characters long.

2.  To change the DeviceNet address, edit the existing address in the 

associated text field (Item G). The DeviceNet address for the 92W 
can be 1 to 63

a.  When changing the address, a warning screen will appear 

indicating this action could disrupt the process. Select 
cancel or continue. 

b.  Select continue and alter the address via number pad and 

select done. A warning screen will appear indicating the 
choice to reset now or reset later. Resetting the device 
could disrupt the process.

c.  Selecting reset now will implement the address change of 

the device.

d.  Selecting reset later will not implement device address 

change until selecting reset slave (Item F) and will cause 
the device address to indicate pending status.

3.  To change the device baud rate (Item H), select the desired rate 

from the choices. The device default baud rate is 125K.

a.  When changing the baud rate, a warning screen will 

appear indicating this action could disrupt the process. 
Select reset now or reset later. 

b.  Selecting reset now will implement the change to the 

baud rate of the device. 

c.  Selecting reset later will not implement the change to the 

baud rate of the device until selecting reset slave.

4.  Selecting reset slave will cause a warning screen to appear 

indicating resetting the device could disrupt the process. Select 
continue to implement changes made to the device address and/
or device baud rate.

Changing the device tag or address on an ASi unit

1.  To change the tag, edit the existing tag in the associated text field 

(Item M). The tag can be up to sixteen characters long.

2.  To change the AS-i address, edit the existing address in the 

associated text field (Item N). The AS-i address for the 97W can be 
0A to 31A or 0B to 31B.

a.  When changing the address, a warning screen will appear 

indicating this action could disrupt the process. Select 
cancel or continue. 

b.  Select continue and alter the address via number pad and 

select done.

Forcing the solenoids on/off

Forcing a solenoid on or off will override master control if wireless link 
overrides are enabled. 
1.  The solenoid control state is forced on or forced off when it is 

highlighted in orange (Item J).

a.  Warning screen will appear indicating this action could 

disrupt the process. Select cancel or continue. 

b.  Select continue and when a solenoid is on, a yellow light 

will illuminate next to the solenoid (Item K).

c.  Select continue and when a solenoid is off, no light will 

illuminate next to the solenoid (Item L).

Setting the valve position

Forcing the solenoid on and off is one way of actuating the valve 
when setting the open and closed positions.
1.  To set a valve to the closed position:

a.  Actuate the valve to the CLOSED position. This can be done 

by forcing the solenoid(s) on or off.

b.  Select set closed. A warning screen will appear indicating 

this action could disrupt the process. Select cancel or 
continue. 

c.  Select continue and the red closed light will illuminate 

(Item I). 

d.  The valve now remembers the current position as the 

closed position.

2.  To set a valve to the open position:

a.  Actuate the valve to the OPEN position. This can be done 

by forcing the solenoid(s) on or off.

b.  Select set open. A warning screen will appear indicating 

this action could disrupt the process. Select cancel or 
continue. 

c.  Select continue and the green open light will illuminate 

(Item I). 

d.  The valve now remembers the current position as the open 

position.

Содержание Axiom AN

Страница 1: ...Axiom AN by StoneL Installation maintenance and operating instructions StoneL publication 105410revD 7 AN 70 en 03 2021...

Страница 2: ...m AN assembly figure 8 3 Maintenance repair and installation 9 3 1 Maintenance and repair 9 3 2 Installation 9 3 3 Specific conditions of use 9 4 Function specific details 10 4 1 Sensor switching modu...

Страница 3: ...rtain about the use of this device or its suitability for your intended use please contact StoneL for assistance 1 3 CE markings The limit switch meets the requirements of European Directives and has...

Страница 4: ...istance from original set point where switch will de energize Max rotational range 120 Terminal block specifications Recommended torque 4 42 in lbs 0 5 Nm Conductor strip length 0 22 0 25 in 5 5 6 5 m...

Страница 5: ...luminum Polysulfone Nitrile compound Nitrile compound 316 stainless steel Solenoid coil specifications 35S 35W Operating voltage Power consumption Inrush current Filtration requirements 20 250 VAC 50...

Страница 6: ...Dimensions Note Axiom AN certified dimensional drawing can be found at www stonel com E3 E2 S1 1 4 NPT 3 0 8 Cv or 3 8 NPT 3 1 2 Cv 1 2 NPT 2 M20 2 3 4 NPT 2 or M25 2 2 3 4 90 in 125 mm 1 4 NPT 2 2 48...

Страница 7: ...the visual indicator drum retaining screw Item E Leave screw loose in order to facilitate indexing of the visual indicator 4 With the actuator in the closed position center the visual indicator drum...

Страница 8: ...ug Internal ground lug provided C Body screws 4 D Trigger E Visual indicator drum retaining screw F Visual indicator drum G Visual indicator drum coupler H Visual indicator drive block I Air manifold...

Страница 9: ...d a minimum of 1 4 turn after cover engages o ring Do not use any tool to tighten the cover WARNING Solenoid power supplied must be limited with a fuse or circuit breaker rated to 2 Amps maximum Field...

Страница 10: ...WR 2 Solenoid 1 Power Open Closed Manual Solenoid 2 Power SET OPEN SET CLOSED OPEN NO OPEN C CLOSED NO CLOSED C SOL 2 PWR 1 SOL 2 PWR 2 1 2 3 4 5 6 7 8 Setup Instructions Operate actuator to closed po...

Страница 11: ...odule operation 4 1 1 SST N O sensor 35S 35W continued Specifications for Wireless Link Communication Bluetooth technology single mode not compatible with Bluetooth Classic Frequency band 2 402 2 480...

Страница 12: ...or single coil unit NAMUR SOL PWR SOL PWR Solenoid Power Closed Open Manual SET OPEN SET CLOSED not used OPEN OPEN not used CLOSED CLOSED 1 2 3 4 5 6 7 8 Setup Instructions Operate actuator to closed...

Страница 13: ...1 Power Closed Open Manual SET OPEN SET CLOSED not used OPEN OPEN not used CLOSED CLOSED 1 2 3 4 5 6 7 8 Setup Instructions Operate actuator to closed position and touch SET CLOSED for 2 seconds Oper...

Страница 14: ...tting instructions Power must be applied to both sensors to ensure proper circuit operation Use a 24 VDC power supply A series load resistor is not required when bench testing 1 Connect 24 VDC to the...

Страница 15: ...StoneL publication 105410revD 7 AN 70 en Axiom AN 15...

Страница 16: ...are assigned Default baud rate 125K software selectable 125K 250K or 500K baud Messaging Polling cyclic and change of state DeviceNet type 100 Bit mapping Inputs 3 bytes Byte 0 bit 0 red LED valve clo...

Страница 17: ...t 2 to 1 in the desired unit Once the correct unit has been physically located on the network indicated by the winking of the LEDs set byte 0 bit 2 back to 0 Performing this function will not change t...

Страница 18: ...D F IO 4 ID1 F ID2 E S 4 F E Bit assignment Inputs Bit 0 aux input 1 Bit 1 aux input 2 Bit 2 green LED valve open Bit 3 red LED valve closed Outputs Bit 0 not used Bit 1 not used Bit 2 OUT 1 Bit 3 OUT...

Страница 19: ...open position 5 Press and hold SET OPEN button until green LED is lit 2 seconds Release button 6 Setpoints are retained even after power is removed A functioning AS Interface network is required to t...

Страница 20: ...ID2 E S 7 A E Bit assignment Inputs Bit 0 red LED valve closed Bit 1 green LED valve open Bit 2 aux input 1 Bit 3 aux input 2 Outputs Bit 0 OUT 1 Bit 1 OUT 2 Bit 2 wireless link enabled Bit 3 not ava...

Страница 21: ...er Solid green Normal operation Flashing red green Output shorted Flashing red green No magnet detected Flashing red green Internal sensor fault sensor may need replacing Flashing yellow red No data e...

Страница 22: ...le 2 The device list export allows you to export valve tag number device address baud rate if applicable valve actuator description valve position stroke time cycle count data and additional informati...

Страница 23: ...mplement changes made to the device address and or device baud rate Changing the device tag or address on an ASi unit 1 To change the tag edit the existing tag in the associated text field Item M The...

Страница 24: ...ates how many cycles the valve has made since last reset Item S A cycle is considered to be a complete actuation of the valve Selecting the reset button Item U will erase the cycle count and start cou...

Страница 25: ...user body or set the device to lower output power if such function is available This transmitter must not be co located or operating in conjunction with any other antenna or transmitter 5 7 2 Industri...

Страница 26: ...hing internal override 0 8 Cv E Internal momentary override only 1 2 Cv Y External momentary internal override 1 2 Cv G External latching internal override 1 2 Cv X Special ENCLOSURE Clear cover Alumi...

Страница 27: ...EN 62026 3 2009 EN 62311 2008 EN 62479 2010 EN 301 489 1 v2 2 0 2017 03 EN 301 489 17 v3 2 0 2017 03 EN 300 328 v2 2 2 2019 07 2809 ATEX II 2 G Ex db IIC T5 Gb ATEX II 2 G Ex db IIC T6 Gb ANX Series...

Страница 28: ...emale cordset and the use of tool secured Turck lokfast guard is required ANabcdefg h Valve Position Monitor When e Connector 10 11 13 15 18 19 20 21 or 22 The Turck minifast and eurofast male recepta...

Страница 29: ...uity between conduit and ground terminal 9 Resistance between Intrinsic Safe Ground and earth ground must be less than one ohm Specific Conditions of Use 1 Part of the enclosure is constructed from pl...

Страница 30: ...ce between Intrinsic Safe Ground and earth ground must be less than one ohm Specific Conditions of Use 1 Part of the enclosure is constructed from plastic To prevent the risk of electrostatic sparking...

Страница 31: ...lectrical continuity between conduit and ground terminal 9 Resistance between Intrinsic Safe Ground and earth ground must be less than one ohm Specific Conditions of Use 1 Part of the enclosure is con...

Страница 32: ...A Tel 1 218 739 5774 stonel com Subject to change without prior notice Neles Jamesbury and Easyflow by Neles StoneL and certain other trademarks are either registered trademarks or trademarks of Neles...