StoneL publication 105410revD
7 AN 70 en
Axiom AN |
13
4.1.2
NAMUR sensor (45S) dual coil
Specifications
Configuration
(2) NAMUR sensors (EN 60947-5-6; IS)
Voltage range
5 - 25 VDC
Current ratings
Target present
Target absent
current < 1.0 mA
current > 2.1 mA
Use with intrinsically safe repeater barrier. NAMUR sensors conform to EN 60947-5-6 standard.
Wiring diagrams
Common receptacle options pin-out for single coil unit
NAMUR
SOL1 PWR +
SOL1 PWR -
Solenoid 1
Power
Closed
Open
Manual
SET
OPEN
SET
CLOSED
not used
OPEN +
OPEN -
not used
CLOSED -
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Setup Instructions:
Operate actuator to closed
position and touch SET CLOSED
for 2 seconds.
Operate actuator to open position
and touch SET OPEN for 2 seconds.
SOL1 OUT
+
13
12
-
Solenoid 2
Power
SOL2 OUT
+
15
14
-
SOL2 PWR -
(1
1)
SOL2 PWR +
(10)
(9)
not used
Reference controlled installation drawing #105412 for
proper intrinsic safe installation details. Find document
in the Appendix on page 29.