StoneL Axiom AN Скачать руководство пользователя страница 1

Axiom

 AN by StoneL

Installation, maintenance and

operating instructions

StoneL publication 105410revD

7 AN 70 en  –  03/2021

Содержание Axiom AN

Страница 1: ...Axiom AN by StoneL Installation maintenance and operating instructions StoneL publication 105410revD 7 AN 70 en 03 2021...

Страница 2: ...m AN assembly figure 8 3 Maintenance repair and installation 9 3 1 Maintenance and repair 9 3 2 Installation 9 3 3 Specific conditions of use 9 4 Function specific details 10 4 1 Sensor switching modu...

Страница 3: ...rtain about the use of this device or its suitability for your intended use please contact StoneL for assistance 1 3 CE markings The limit switch meets the requirements of European Directives and has...

Страница 4: ...istance from original set point where switch will de energize Max rotational range 120 Terminal block specifications Recommended torque 4 42 in lbs 0 5 Nm Conductor strip length 0 22 0 25 in 5 5 6 5 m...

Страница 5: ...luminum Polysulfone Nitrile compound Nitrile compound 316 stainless steel Solenoid coil specifications 35S 35W Operating voltage Power consumption Inrush current Filtration requirements 20 250 VAC 50...

Страница 6: ...Dimensions Note Axiom AN certified dimensional drawing can be found at www stonel com E3 E2 S1 1 4 NPT 3 0 8 Cv or 3 8 NPT 3 1 2 Cv 1 2 NPT 2 M20 2 3 4 NPT 2 or M25 2 2 3 4 90 in 125 mm 1 4 NPT 2 2 48...

Страница 7: ...the visual indicator drum retaining screw Item E Leave screw loose in order to facilitate indexing of the visual indicator 4 With the actuator in the closed position center the visual indicator drum...

Страница 8: ...ug Internal ground lug provided C Body screws 4 D Trigger E Visual indicator drum retaining screw F Visual indicator drum G Visual indicator drum coupler H Visual indicator drive block I Air manifold...

Страница 9: ...d a minimum of 1 4 turn after cover engages o ring Do not use any tool to tighten the cover WARNING Solenoid power supplied must be limited with a fuse or circuit breaker rated to 2 Amps maximum Field...

Страница 10: ...WR 2 Solenoid 1 Power Open Closed Manual Solenoid 2 Power SET OPEN SET CLOSED OPEN NO OPEN C CLOSED NO CLOSED C SOL 2 PWR 1 SOL 2 PWR 2 1 2 3 4 5 6 7 8 Setup Instructions Operate actuator to closed po...

Страница 11: ...odule operation 4 1 1 SST N O sensor 35S 35W continued Specifications for Wireless Link Communication Bluetooth technology single mode not compatible with Bluetooth Classic Frequency band 2 402 2 480...

Страница 12: ...or single coil unit NAMUR SOL PWR SOL PWR Solenoid Power Closed Open Manual SET OPEN SET CLOSED not used OPEN OPEN not used CLOSED CLOSED 1 2 3 4 5 6 7 8 Setup Instructions Operate actuator to closed...

Страница 13: ...1 Power Closed Open Manual SET OPEN SET CLOSED not used OPEN OPEN not used CLOSED CLOSED 1 2 3 4 5 6 7 8 Setup Instructions Operate actuator to closed position and touch SET CLOSED for 2 seconds Oper...

Страница 14: ...tting instructions Power must be applied to both sensors to ensure proper circuit operation Use a 24 VDC power supply A series load resistor is not required when bench testing 1 Connect 24 VDC to the...

Страница 15: ...StoneL publication 105410revD 7 AN 70 en Axiom AN 15...

Страница 16: ...are assigned Default baud rate 125K software selectable 125K 250K or 500K baud Messaging Polling cyclic and change of state DeviceNet type 100 Bit mapping Inputs 3 bytes Byte 0 bit 0 red LED valve clo...

Страница 17: ...t 2 to 1 in the desired unit Once the correct unit has been physically located on the network indicated by the winking of the LEDs set byte 0 bit 2 back to 0 Performing this function will not change t...

Страница 18: ...D F IO 4 ID1 F ID2 E S 4 F E Bit assignment Inputs Bit 0 aux input 1 Bit 1 aux input 2 Bit 2 green LED valve open Bit 3 red LED valve closed Outputs Bit 0 not used Bit 1 not used Bit 2 OUT 1 Bit 3 OUT...

Страница 19: ...open position 5 Press and hold SET OPEN button until green LED is lit 2 seconds Release button 6 Setpoints are retained even after power is removed A functioning AS Interface network is required to t...

Страница 20: ...ID2 E S 7 A E Bit assignment Inputs Bit 0 red LED valve closed Bit 1 green LED valve open Bit 2 aux input 1 Bit 3 aux input 2 Outputs Bit 0 OUT 1 Bit 1 OUT 2 Bit 2 wireless link enabled Bit 3 not ava...

Страница 21: ...er Solid green Normal operation Flashing red green Output shorted Flashing red green No magnet detected Flashing red green Internal sensor fault sensor may need replacing Flashing yellow red No data e...

Страница 22: ...le 2 The device list export allows you to export valve tag number device address baud rate if applicable valve actuator description valve position stroke time cycle count data and additional informati...

Страница 23: ...mplement changes made to the device address and or device baud rate Changing the device tag or address on an ASi unit 1 To change the tag edit the existing tag in the associated text field Item M The...

Страница 24: ...ates how many cycles the valve has made since last reset Item S A cycle is considered to be a complete actuation of the valve Selecting the reset button Item U will erase the cycle count and start cou...

Страница 25: ...user body or set the device to lower output power if such function is available This transmitter must not be co located or operating in conjunction with any other antenna or transmitter 5 7 2 Industri...

Страница 26: ...hing internal override 0 8 Cv E Internal momentary override only 1 2 Cv Y External momentary internal override 1 2 Cv G External latching internal override 1 2 Cv X Special ENCLOSURE Clear cover Alumi...

Страница 27: ...EN 62026 3 2009 EN 62311 2008 EN 62479 2010 EN 301 489 1 v2 2 0 2017 03 EN 301 489 17 v3 2 0 2017 03 EN 300 328 v2 2 2 2019 07 2809 ATEX II 2 G Ex db IIC T5 Gb ATEX II 2 G Ex db IIC T6 Gb ANX Series...

Страница 28: ...emale cordset and the use of tool secured Turck lokfast guard is required ANabcdefg h Valve Position Monitor When e Connector 10 11 13 15 18 19 20 21 or 22 The Turck minifast and eurofast male recepta...

Страница 29: ...uity between conduit and ground terminal 9 Resistance between Intrinsic Safe Ground and earth ground must be less than one ohm Specific Conditions of Use 1 Part of the enclosure is constructed from pl...

Страница 30: ...ce between Intrinsic Safe Ground and earth ground must be less than one ohm Specific Conditions of Use 1 Part of the enclosure is constructed from plastic To prevent the risk of electrostatic sparking...

Страница 31: ...lectrical continuity between conduit and ground terminal 9 Resistance between Intrinsic Safe Ground and earth ground must be less than one ohm Specific Conditions of Use 1 Part of the enclosure is con...

Страница 32: ...A Tel 1 218 739 5774 stonel com Subject to change without prior notice Neles Jamesbury and Easyflow by Neles StoneL and certain other trademarks are either registered trademarks or trademarks of Neles...