Installation examples
A-C-E: Boiler control via 0-10VDC + cascade via low loss header
43
A-C-E: Boiler control via 0-10VDC + cascade via low loss header
Description
2
x R40 with low loss header
Cascade control
Tips
Complete accessory kits with low loss
header are available for
∆
T=10-20K
(see chapter
"
Accessories
"
).
The primary circuit should be
de
signed for
∆
T=20K, this guarantees
a
high boiler efficiency.
When the sec
o
ndary circuit is
de
signed for a
∆
T smaller than 20K,
the
flow temperature in the header will
be
lower than the flow temperature of
the
boiler. This should be taken in
to
consid
eration during the design stage.
The header should be positioned
close to the boiler, to avoid a negative
influ
e
nce on the temperature control
quality.
In case of a boiler room installed on
the roof, the boiler may never be
hy
draulically connected at the highest
point of the installation.
Содержание ECONOFLAME R40
Страница 25: ... R40 65 85 R40 100 150 Accessories Dimensions single low loss header 25 ...
Страница 53: ...Notes 55 ...