background image

OPErATiON 

 

maintenance and care

6

 | WPL-A  Premium 

www.stiebel-eltron.com

5.  Maintenance and care

 

Material losses

Only qualified contractors may perform maintenance 

work, such as electrical safety checks.

A damp cloth is sufficient for cleaning all plastic and sheet metal 

parts. Never use abrasive or corrosive cleaning agents.
Regularly check the condensate drain (visual inspection). Remove 

any contaminants and blockages immediately.

1.

2.

1

D

00000

37

83

1

1  Inspection port

 

Material losses

Keep the air discharge and intake apertures free from 

snow and leaves.

Remove any leaves or other foreign bodies from the evaporator 

fins periodically.
We recommend a regular inspection (to establish the current con-

dition of the system), and maintenance by a qualified contractor 

as required (to restore the system to the ideal condition).

6.  Troubleshooting

fault

Cause

remedy

There is no hot 

water or the 

heating system 

remains cold. 

 

 

 

 

No power at the appliance. 

 

 

 

 

 

 

 

Check the fuses / MCBs in 

your fuse box / distribution 

board. Replace the fuses/

reset the MCBs if required. 

Notify your qualified 

contractor if the fuses/

MCBs blow/trip again after 

switching the system back 

on.

Water is leaking 

from the appli-

ance.

The condensate drain may be 

blocked. 

Clean the condensate drain 

as described in "Mainte-

nance and care".

The heater gets 

warm, but the 

rooms are not 

heated to the 

required temper-

ature.

The dual mode temperature is 

set too low. 

 

 

 

Increase the dual mode 

temperature to e.g. 0 °C. 

 

 

 

 

 

 

 

The building is a new build 

and is in the screed drying 

phase. 

 

Increase the dual mode 

temperature to +5 °C. 

After 1 to 2 years the dual 

mode temperature can be 

reset to e.g. -3 °C.

fault

Cause

remedy

There is a loss of 

pressure in the 

heating system. 

 

 

Water drips from the safety 

valve. 

 

 

 

Use the inspection port 

to check whether water 

is passing from the safety 

valve hose into the conden-

sate pan. Call your quali-

fied contractor.

Condensate is 

collecting on the 

outside of the 

appliance. 

 

 

 

The heat pump extracts heat 

from the outdoor air in order 

to heat the building. This can 

cause the humidity in the 

outdoor air to accumulate as 

dew or frost on the cooled 

heat pump casing. This is not 

a defect.

 

 

 

 

 

 

 

The fan runs 

when the 

compressor is 

switched OFF. 

 

 

 

 

 

 

 

At outside temperatures below 

10 °C, the fan is regularly 

started at the lowest speed 

when the compressor is idle. 

This prevents the evaporator 

and fan from freezing or icing 

up due to water draining 

off. At temperatures above 

the freezing point, the time 

between two defrost cycles is 

increased, thereby improving 

overall efficiency.

 

 

 

 

 

 

 

 

 

 

 

The appliance 

produces rhyth-

mic scraping or 

grinding noises.

Ice has formed on the air 

grille, on the fan blades or in 

the air routing. 

Call your qualified contrac-

tor (see chapter "Installa-

tion / Troubleshooting / Fan 

noise").

 

Note

Even when the condensate is draining away correctly, it 

is not unusual for water to drip from the appliance onto 

the floor.

If you cannot remedy the fault, contact your qualified contractor. 

To facilitate and speed up your request, provide the number from 

the type plate. The type plate is located at the front top, on the 

right or left-hand side of the casing.

Sample type plate

Montageanweisung beachten! Dichtheit geprüft! 

Made in Germany

*xxxxxxxxxxxxxxxxxx

*

26

0

3

01

1

73

6

1

1  Number on the type plate

Содержание WPL-A 05 HK 230 Premium

Страница 1: ...OPERATION AND INSTALLATION Air source heat pump WPL A 05 HK 230 Premium WPL A 07 HK 230 Premium...

Страница 2: ...14 10 1 Transport 14 10 2 Heating water connection 14 10 3 Flow and return connection 15 10 4 Fitting the push fit connectors 15 10 5 Oxygen diffusion 16 10 6 Filling the heating system 16 10 7 Conden...

Страница 3: ...r gised for 2 minutes until the inverter capaci tors have discharged Never interrupt the power supply even out side the heating season The system s active frost protection is not guaranteed if the pow...

Страница 4: ...the system configuration the age of the system and the flow rates Confirmation of the specified output data can only be obtained if the test conducted for this purpose is also performed in accord ance...

Страница 5: ...ondenser transfers the heat to the heating circuit The refrigerant then expands again and the cycle restarts from the beginning At air temperatures below approx 7 C the humidity in the air condenses a...

Страница 6: ...e the dual mode temperature to 5 C After 1 to 2 years the dual mode temperature can be reset to e g 3 C Fault Cause Remedy There is a loss of pressure in the heating system Water drips from the safety...

Страница 7: ...B BE Remote control FET Remote control FE7 Ribbon heater HZB 1 Ribbon heater HZB 2 High limit safety cut out for area heating system STB FB Heating circuit pump UP 25 7 5 PCV T support SK 1 Wall mount...

Страница 8: ...air or other ventilation equipment In order to comply with the appliance s safety concept safety clearances to light wells must be observed Installation on foundation light well at ground level 1000 1...

Страница 9: ...liance and facilitate maintenance work D0000096921 f Never install the appliance in a recess Two sides of the ap pliance must remain exposed Material losses Please note that both the flow of outdoor a...

Страница 10: ...into the building to en sure that they are watertight The supply lines are all electric cables plus the flow and return lines To facilitate connection to the appliance we recommend using flexible supp...

Страница 11: ...ront and back Ensure you are using the correct brackets for the left and right hand slots respectively f Position the brackets so that the groove on the bracket is hooked into the appliance f Secure t...

Страница 12: ...ories with which the appliance was secured to the transport pallet D0000064201 f Hook two brackets respectively into the lateral slots on the front and back Ensure you are using the correct brackets f...

Страница 13: ...fer cylinder to ensure trouble free appliance operation The buffer cylinder provides hydraulic separation of the volume flows in the heat pump circuit and heating circuit and also serves as an energy...

Страница 14: ...nnected without removing the cover or side panels 10 1 Transport f When transporting the appliance be aware of its centre of gravity The centre of gravity is in the area where the compressor is locate...

Страница 15: ...17 0 5 mm Pipe diameter 28 mm 21 0 5 mm How the push fit connectors work The push fit connectors are equipped with a retainer with stain less steel serrations and an O ring for sealing The push fit co...

Страница 16: ...recommended in order to prevent corrosion Note Suitable appliances for water softening and desalinating as well as for filling and flushing heating systems can be obtained from trade suppliers Note Do...

Страница 17: ...to drain off 26_03_01_1868 1 1 Condensate drain f Observe chapter Electrical connection Ribbon heater f If the appliance is sited on foundations the condensate drips freely into the condensate drain p...

Страница 18: ...tion f Before working on the appliance isolate it from the power supply at the control panel Note The terminals are located in the terminal area of the ap pliance f Follow the instructions in the chap...

Страница 19: ...ation and the provision of high DHW temperatures Emergency mode If the heat pump shuts down due to a fault the heating output is covered by the electric emergency booster heater Heat up program only...

Страница 20: ...ated washer f Connect the following components to the heat pump manag er in accordance with the technical guides Circulation pump for the heat consumer side Outside temperature sensor Return sensor on...

Страница 21: ...safety cut out has tripped 26_03_01_1880 1 26_03_01_1880 1 Electric emergency booster heater f Remove the cause of the fault D0000035383 f Reset the high limit safety cut out by pressing the reset bu...

Страница 22: ...meter WP WATER FLOW RATE INFO HEAT PUMP PROCESS DATA f Compare the value with the minimum flow rate see chapter Specification Data table Minimum flow rate has been reached No further measures required...

Страница 23: ...you to adjust the heating curve cor rectly Fully open thermostatic or zone valves in a lead room e g living room and bathroom We do not recommend installing thermostatic or zone valves in the lead ro...

Страница 24: ...gh the emergency booster heater This will result in higher running costs f Switch the appliance off in the heat pump manager Parameter HEAT PUMP OFF COMMISSIONING SILENT MODE 13 4 Other settings f For...

Страница 25: ...ow and ice Remove any leaves or other foreign bodies from the evaporator fins periodically 17 Troubleshooting WARNING Electrocution f Before working on the appliance isolate it from the power supply a...

Страница 26: ...r If the appliance is operated in dual mode operation with an ex ternal second heat generator or as a module with a further heat pump set the DIP switch as shown WP Typ ON 1 2 3 4 D0000057055 DIP swit...

Страница 27: ...26_03_01_1880 1 Electric emergency booster heater f Remove the cause of the fault D0000035383 f Reset the high limit safety cut out by pressing the reset but ton f Check whether the heating water is...

Страница 28: ...270 1160 900 70 593 g01 g02 D0000034131 WPL A 05 HK 230 Premium WPL A 07 HK 230 Premium e01 Heating flow Type of connection Plug in connection Plug in connection Diameter mm 28 28 e02 Heating return T...

Страница 29: ...Installation Specification www stiebel eltron com WPL A Premium 29...

Страница 30: ...BF01 XE22 XD03 XD01 XD06 XD02 PE GND A B U V W MSD1 MSP3 L N PE 1 2 MP2 MSD8 XE19 PE N L Netzversorgung Inverter Abtauventil N Abtauventil L Verdichter ON PE Begleitheizung N Begleitheizung L lsumpfh...

Страница 31: ...1 N DHC 1 L DHC 2 N DHC 2 L 12 18V ND 4 20mA 12 18V HD 4 20mA CAN GND CAN L CAN H 12V Phase 4 Phase 3 Phase 2 Phase 1 12V Phase 4 Phase 3 Phase 2 Phase 1 Hei gastemperatur GND Hei gastemperatur Heizu...

Страница 32: ...5 Split ferrite RF06 Split ferrite RF07 Split ferrite XD01 External heat pump power supply terminal XD02 External NHZ terminal XD03 External control terminal XD05 External bus terminal XD06 External r...

Страница 33: ...4 6 8 10 12 25 20 15 10 5 0 5 10 15 20 2 3 4 5 7 8 9 10 D0000090274 X Outside temperature C 2 Max W65 4 Max W45 7 Min W65 9 Min W45 Y Heating output kW 3 Max W55 5 Max W35 8 Min W55 10 Min W35 DHW ou...

Страница 34: ...12 25 20 15 10 5 0 5 10 15 20 2 3 4 5 7 8 9 10 D0000090269 X Outside temperature C 2 Max W65 4 Max W45 7 Min W65 9 Min W45 Y Heating output kW 3 Max W55 5 Max W35 8 Min W55 10 Min W35 DHW output 0 2 4...

Страница 35: ...35 W18 partial load kW 3 37 4 94 Power consumption Power consumption at A7 W35 EN 14511 kW 0 61 0 61 Power consumption at A2 W35 EN 14511 kW 0 69 1 Power consumption at A 7 W35 EN 14511 kW 1 44 2 36 P...

Страница 36: ...48 148 IP rating IP 14B IP 14B Condenser material 1 4401 Cu 1 4401 Cu Dimensions Height mm 900 900 Width mm 1270 1270 Depth mm 593 593 Weights Weight kg 135 135 Connections Connection heating flow ret...

Страница 37: ...those subsidiaries Such guarantee is only grant ed if the subsidiary has issued its own terms of guarantee No other guarantee will be granted We shall not provide any guarantee for appliances acquire...

Страница 38: ...38 WPL A Premium www stiebel eltron com NOTES...

Страница 39: ...www stiebel eltron com WPL A Premium 39 NOTES...

Страница 40: ...TIEBEL ELTRON OY Kapinakuja 1 04600 M nts l Tel 020 720 9988 info stiebel eltron fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz C dex 3 Tel 0387 7438 88 F...

Отзывы: