iNSTALLATiON
Specification
www.stiebel-eltron.com
WPL-A Premium |
35
18.5 Data table
The performance data apply for new appliances with clean heat exchangers.
The power consumption figures for the integral auxiliary drives are maximum values and may vary subject to operating point.
The power consumption of the integral auxiliary drives is included in the output details of the heat pump (to EN 14511).
WPL-A 05 HK 230 Premium
WPL-A 07 HK 230 Premium
202669
200123
Heating output
Heating output at A7/W35 (min./max.)
kW
2.65/7.40
2.65/10.75
Heating output at A2/W35 (min./max.)
kW
2.10/6.55
2.10/9.70
Heating output at A-7/W35 (min./max.)
kW
2.05/4.97
2.05/6.87
Heating output at A7/W35 (EN 14511)
kW
3.31
3.31
Heating output at A2/W35 (EN 14511)
kW
3.19
4.3
Heating output at A-7/W35 (EN 14511)
kW
4.97
6.87
Heating output at A-7/W55 (EN 14511)
kW
4.94
7.01
Heating output at A-15/W35 (EN 14511)
kW
4.18
6.4
Heating output in reduced night mode A-7/W35
kW
3.4
5.2
Heating output in max. reduced night mode A-7/W35
kW
2.9
2.9
Heating output in reduced night mode A-7/W55
kW
3.2
4.9
Heating output in max. reduced night mode A-7/W55
kW
2.7
2.7
Max. cooling capacity at A35/W7
kW
4.73
7.3
Cooling capacity at A35/W7 partial load
kW
1.81
3.31
Max. cooling capacity at A35/W18
kW
6.86
10.15
Cooling capacity at A35/W18 partial load
kW
3.37
4.94
Power consumption
Power consumption at A7/W35 (EN 14511)
kW
0.61
0.61
Power consumption at A2/W35 (EN 14511)
kW
0.69
1
Power consumption at A-7/W35 (EN 14511)
kW
1.44
2.36
Power consumption at A-7/W55 (EN 14511)
kW
1.97
2.97
Power consumption at A-15/W35 (EN 14511)
kW
1.44
2.4
Power consumption, emergency/booster heater
kW
6.2
6.2
Coefficients of performance
COP at A7/W35 (EN 14511)
5.42
5.42
COP at A2/W35 (EN 14511)
4.6
4.3
COP at A-7/W35 (EN 14511)
3.45
2.93
COP at A-7/W55 (EN 14511)
2.51
2.36
COP at A-15/W35 (EN 14511)
2.9
2.67
SCOP (EN 14825)
4.7
4.88
Max. cooling capacity factor at A35/W7
2.86
2.35
Cooling capacity factor at A35/W7 partial load
2.97
3.02
Max. cooling capacity factor at A35/W18
3.84
2.87
Cooling capacity factor at A35/W18 partial load
4.35
4.28
Sound emissions
Sound power level (EN 12102)
dB(A)
48
48
Sound power level W35 (EN 12102)
dB(A)
48
48
Sound power level W55 (EN 12102)
dB(A)
47
47
Sound power level max.
dB(A)
58
59
Sound power level, reduced night mode
dB(A)
47
51
Sound power level max. reduced night mode
dB(A)
47
47
Application limits
Min. application limit, heat source
°C
-25
-25
Max. application limit, heat source
°C
40
40
Min. application limit on the heating side
°C
15
15
Max. application limit on the heating side
°C
75
75
Application limit heat source at W65
°C
-17
-17
Min. cooling mode application limit for outside temperature
°C
15
15
Max. cooling mode application limit for outside temperature
°C
40
40
Energy data
Energy efficiency class
A+++
A+++
Содержание WPL-A 05 HK 230 Premium
Страница 1: ...OPERATION AND INSTALLATION Air source heat pump WPL A 05 HK 230 Premium WPL A 07 HK 230 Premium...
Страница 29: ...Installation Specification www stiebel eltron com WPL A Premium 29...
Страница 38: ...38 WPL A Premium www stiebel eltron com NOTES...
Страница 39: ...www stiebel eltron com WPL A Premium 39 NOTES...