9.8 Preparing the electrical installation
WARNING Risk of electrocution!
Carry out all electrical connection and installation work
in accordance with national and regional regulations.
WARNING Risk of electrocution!
The connection to the power supply must be in the form
of a permanent connection. The appliance must be able
to be separated from the power supply by an isolator
that disconnects all poles with at least 3 mm contact
separation. This requirement can be met by contactors,
isolators, fuses, etc.
!
Material losses
The specified voltage must match the mains voltage. Ob-
serve the type plate.
!
Material losses
Provide separate fuses for the 3 power circuits (for the
appliance, the electric emergency/booster heater and the
control unit).
f
f
Always connect "L" for the heat pump and the control unit to
the same phase.
Where required, you can install our starting current limiter with
25 A for the WPL 10 AC (see "Additional accessories").
f
f
Route cables with the following cross-sections in accordance
with the respective fuse rating:
MCB/fuse
rating
Assignment
Cable cross-section
C 25 A
Heat pump
(single phase)
2.5 mm² for routing above the surface
4.0 mm² for routing through a wall
C 16 A
Heat pump
(3-phase)
2.5 mm²
B 35 A
Electric emergen-
cy/booster heater
(DHC)
(single phase)
6.0 mm² for routing through a wall
4.0 mm² when routing multi-core cables
on a wall or in an electrical conduit on
a wall
B 16 A
Electric emergen-
cy/booster heater
(DHC)
(3-phase)
2.5 mm
1.5 mm² with only two live cores and
routing on a wall or in an electrical con-
duit on a wall.
B 16 A
Control
1.5 mm²
The electrical data is provided in the chapter "Specification" . You
require a J-Y (St) 2x2x0.8 mm² cable as BUS cable.
10. Installation
10.1 Siting
f
f
When installing the appliance, observe the air intake
direction.
f
f
Position the standard appliance on the prepared substrate.
26
�0
3�
01
�1
54
4
f
f
Remove the cover.
26
�0
3�
01
�1
55
0