9.9 DHW connection
f
Remove the lower front panel (see chapter "Installation /
Transport / Separating the appliance / Removing the lower
front panel").
!
Material losses
f
Carry out all water connection and installation work
in accordance with regulations.
!
Material losses
The DHW outlet connection is prefitted with a plastic
union nut and a soft rubber gasket.
The torque of the plastic union nut depends on the gasket
used.
15 Nm = prefitted soft rubber gasket.
25 Nm = alternative hard gasket.
f
Keep to the permissible torque.
!
Material losses
Operate the appliance only with pressure-tested taps.
9.9.1 Permissible materials
Cold water line
Galvanised steel, stainless steel, copper and plastic are approved
materials.
DHW line
Stainless steel, copper and plastic pipework are approved.
!
Material losses
The maximum permissible pressure must not be exceed-
ed (see chapter "Specification / Data table").
f
Install a type-tested safety valve in the cold water supply
line. Please note that, depending on the supply pressure, you
may also need a pressure reducing valve.
f
The safety valve drain aperture must remain open to atmos-
phere.
f
Install the safety valve drain pipe with a constant fall to the
drain.
f
Size the discharge outlet so that water can drain off unim-
peded when the safety valve is fully opened.
f
Flush the pipes thoroughly.
1
26
0
3
01
1
75
8
1 Drain (DHW cylinder)
f
Fill the DHW cylinder via the drain.
f
Open all downstream draw-off points until the appliance is
full and the pipework is free of air.
f
Carry out a tightness check.
9.10 DHW circulation connection
DHW circulation is not recommended for reasons of poor energy
efficiency. If DHW circulation is required due to unfavourable pipe-
work or for reasons of convenience, you must install the DHW cir-
culation in accordance with applicable standards. To reduce pump
runtime and energy demand, we recommend imposing time and
temperature controls on activation of the DHW circulation pump.
The DHW circulation connector is located at the back of the appli-
ance (see chapter "Specification / Dimensions and connections").
A DHW circulation pump can be found in our range of accessories.
D
00000
39
21
9
1
1 Cap
f
Detach the panel.
f
Remove the foam parts.
f
Unscrew the cap.
f
Reinsert the foam parts.
f
Connect the DHW circulation line.
Содержание WPE-I 04 HKW 230 Premium
Страница 29: ...Installation Specification www stiebel eltron com WPE I H K W 230 Premium 29 ...
Страница 45: ...www stiebel eltron com WPE I H K W 230 Premium 45 NOTES ...
Страница 46: ...46 WPE I H K W 230 Premium www stiebel eltron com NOTES ...
Страница 47: ...www stiebel eltron com WPE I H K W 230 Premium 47 NOTES ...