30
| LWZ 304 Trend | LWZ 404 Trend | LWZ 304 Integral
www.stiebel-eltron.com
INSTALLATION
Settings
Humidity protection ventilation is activated when the ventilation is
switched off (stage 0). The fans are switched off during the first 24
hours after stopping ventilation. The humidity protection function
then checks every hour whether the rooms need to be ventilated.
For this, the fans operate for the duration of the "HUM. MASKING
TIME" at stage 1. If the measured value exceeds the set humidity
level, both fans operate until the set humidity level falls below the
"HUMIDITY HYSTERESIS". The humidity protection becomes active
as soon as the appliance starts following the restoration of the
power supply following a power failure.
A set humidity level function is implemented to protect the build-
ing from condensation forming on the inside of exterior walls. For
this, humidity of 100 % at 20 °C outside temperature is interpolat-
ed with the "HUM. THRESHOLD VALUE" at -10 °C outside temper-
ature. In order to take the type of building and the insulation of
the exterior walls into account, set parameter "HUM. THRESHOLD
VALUE" as follows:
- Brickwork, 25 cm thick, not insulated: 55 % (standard)
- Brickwork, 25 cm thick, 10 cm external insulation: 75 %
Fan output correction (stage 1/2/3) subject to humidity
For output stages 1, 2 and 3, the qualified contractor can activate
a correction subject to humidity that orients itself on the internal
relative humidity. This enables an increase in the air flow rate
when the relative humidity is higher.
In winter, an excessively high air flow rate can contribute to the
ambient air becoming too dry. This can be counteracted by a re-
duction of the air flow rate subject to the prevailing humidity level.
"SET HUMIDITY MIN": This parameter sets the lower limit of rel-
ative humidity.
"SET HUMIDITY MAX": This parameter sets the upper limit of rel-
ative humidity.
"OUTPUT INCREASE": This parameter determines the percentage
by which the fan output is to be increased, if the value set in the
"SET HUMIDITY MAX" parameter is exceeded by a margin greater
than the "HUMIDITY HYSTERESIS".
"OUTPUT REDUCTION": This parameter determines the percentage
by which the fan output is to be reduced, if the value set in the "SET
HUMIDITY MIN" parameter is not reached by a margin greater than
the "HUMIDITY HYSTERESIS". In the delivered condition, "OUTPUT
INCREASE" and "OUTPUT REDUCTION" are set to 0 %. This disables
the correction of fan output subject to humidity. The percentage
entered with the "OUTPUT INCREASE" and "OUTPUT REDUCTION"
parameters relates to the maximum fan output and not to the
currently selected fan output.
OVEN / FIREPLACE
If operating combustion equipment in the accommodation, you
can go to the "OVEN / FIREPLACE" menu to set how the ventilation
unit responds when a signal transmitter is connected to terminal
X4-13/14, connection Oven / fireplace, which switches when the
combustion equipment is operated.
MAIN MENU
VENTILATION
26
0
4
01
0
37
3
OVEN / FIREPLACE
N/O CONTACT OFF
N/C CONTACT OFF
N/O MONITORING.
N/C MONITORING
OFF
In the "OVEN / FIREPLACE" menu there are five options, of which
only one can ever be enabled at a time (indicated by a filled box).
If you select a new option, the current setting will be disabled.
Option
Effect
OFF
No action
N/O CONTACT OFF With a 230 V input signal, the supply air fan, extract air
fan, exhaust air fan and compressor are switched off.
N/C CONTACT OFF
With a 0 V input signal, the supply air fan, extract air
fan, exhaust air fan and compressor are switched off.
N/O MONITORING
With a 230 V input signal, the extract air fan, exhaust air
fan and compressor are switched off when the supply air
fan stops.
N/C MONITORING
With a 0 V input signal, the extract air fan, exhaust air
fan and compressor are switched off when the supply air
fan stops.
AIR/AIR HE (air/air heat exchanger)
MAX DEFROST DUR.
Defrost terminates if, during defrosting the air/air heat exchang-
er, the maximum defrost duration is exceeded.
DEFR START THRESHOLD
Here, you specify the speed change (in %) from which defrost
begins.
FILTER SPEED
The air flow rate is continuously adjusted. If the filter is dirty, the
fan speed increases. If it is above the start value by the set value
(in %), the filter symbol shows that the filter is dirty.
SERVICE
RUNTIME FILTER
This value indicates how many days have passed since the last
filter reset.
RESET FILTER
When you set this parameter to "ON", a filter reset will be trig-
gered.