25
04/13424999763
Wind and rain detector WRM/2 24V and Rain detector RM/2 24V
Connection and adjustment options
DIP 2
Activation in the event of rain
For certain situations the rain detector can be switched off via DIP-Switch 2.
ON
Rain detector in operation. Activation in the event of rain.
OFF
Rain detector deactivated. No activation in the event of rain.
DIP 3
Pulse output
For certain situations wind and rain detection can be switched to continuous signal or pulse signal via
DIP-Switch 3.
ON
Pulse signal setting: signal contact will be reset after approx. 1 sec.
OFF
Continuous pulse signal setting: output remains connected while the weather conditions are wet or
windy.
DIP 4
Wind delay
DIP-Switch 4 is used to set the length of time (interval) for which the wind must remain at the pre-
programmed wind speed before the system closes the windows.
ON
Level 2 (switch-on delay 20 seconds)
OFF
Level 1 (switch-on delay 10 seconds)
DIP 5
Higher wind trigger threshold
This DIP-Switch can be used to set the wind speed at which the windows should close.
DIP 6
Lower wind trigger threshold
This DIP-Switch can be used to set the wind speed at which the windows should close.
Wind trigger threshold
Threshold value (level)
Wind speed
DIP 5
OFF
+ DIP 6
OFF
Level 0
approx. 7 m/s
DIP 5
OFF
+ DIP 6
ON
Level 1
approx. 10 m/s
DIP 5
ON
+ DIP 6
OFF
Level 2
approx. 13 m/s
DIP 5
ON
+ DIP 6
ON
Level 3
approx. 15 m/s
DIP 7
Wind pulse output
DIP-Switch 7 can be used to give the wind pulse output from a cup anemometer. (Suitable for WRZ
control units).
ON
Wind pulse output is switched on.
OFF
Wind pulse output is deactivated.