2-40 HP Portable Chillers
Chapter 7: Appendix
49 of 70
2 hp and 3.5 hp Water-Cooled Portable Chillers
Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton
(9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water.
For 50 Hz applications
, multiply capacity by
0.83
.
Nominal 60
Hz capacity flow rate must be maintained.
Nominal
Condenser
water
Nominal cooling
water
Com- Nominal
Water
flow in gpm
Amp draws
g
HP capacity
c
in tons
flow
pressor
pump
conn.
Tower
City
460/3/60
h
no pump
1 pump
gpm
d
hp hp in.
NPT
water
e
water
f
rated running
2 2.1 1.9 5.1
2.0
1.0
1.0” 6.2 4.2 12.2 8.3
3.5 3.6 3.4 8.6
3.5 1.0 1.0” 10.5 7.2
16.4
11.8
c
Based on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water. Optional additional process
pump hp (kW) reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power).
d
Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump.
e
Based on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum.
f
Based on availability of 70ºF (21ºC) city water at 25 psi (172.4 kPa/1.7 bars) minimum.
g
An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total
chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1
on page 16), and add it to the chiller rated or running amperage.
h
Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages.
2 hp and 3.5 hp water-cooled portable chillers come standard with 2” (63 mm) swivel casters.
Process
Weights
HP
Compressor connections
Dimensions in inches
c
Dry
d
Shipping
d
Operating
d
e
hp
in.
NPT
height
width
depth
lbs.
lbs. lbs.
2 2.0 1.0”
28.3”
22.0” 41.7” 333
363
383
3.5 3.5 1.0” 28.3”
22.0” 41.7” 362
392
412
c
To convert to
cm
, multiply by
2.54
. Add to height dimension based on mounting options.
d
Weight is for standard chiller. Some optional features will increase weight. Multiply by
0.454
to calculate
Kg
.
e
Operating weight is with a full 6-gallon (
22.7 liter
) reservoir tank of water.