2-40 HP Portable Chillers
Chapter 4: Operation
29 of 70
Chapter 4: Operation
4-1 Panel Buttons, Indicator Lights, and Switches
Microprocessor Controllers
Standard chillers use a microprocessor-based PID controller. These controllers are modular,
self-contained units that can slide from their mounting housing. They are factory set and
adjusted; no field adjustment to the internal controls are necessary. Their standard operation
range is 30ºF to 65ºF (-1ºC to 18ºC). See Figure 7: Typical Portable Chiller Microprocessor
Controller.
E5CK Controller
Indicator
Name
Description
PV
8.8.8.8
Process Value
LED
During normal operation, the top LED display on
the controller displays the actual process
temperature. It also lists parameter symbols during
setup and error messages if an error occurs.
SV
8.8.8.8
Set Value LED
During normal operation, the green bottom LED
display on the controller displays the process set
point you want the chiller to maintain. It also
displays parameter and pre-set function values
during set up.
OUT1
Out 1 LED
The orange OUT1 LED lights when the control
output energizes the hot-gas bypass solenoid
valve.
OUT2
Out 2 LED
The orange OUT2 LED lights whenever the
process temperature is four degrees or more above
the “To Process” setpoint. The compressor then
comes on and runs until the temperature at the “To
Process” thermocouple is three degrees below the
setpoint.
MANU
MANU LED
The orange MANU LED is not used and does not
light.
STOP
Stop LED
The orange STOP LED is not used.
RMT
RMT LED
The orange RMT LED is lit during remote
communication operation.
AT
AT LED
The orange AT LED flashes during auto-tuning.
Содержание A0554831
Страница 59: ...2 40 HP Portable Chillers Chapter 7 Appendix 59 of 70 50 Hertz Pump Curves DWG No S0554823...
Страница 62: ...2 40 HP Portable Chillers Chapter 7 Appendix 62 of 70 7 5 Remote Air Cooled Chiller Configurations...
Страница 65: ...2 40 HP Portable Chillers Chapter 7 Appendix 65 of 70 Typical Piping Schematic 2 and 3 1 2 hp Models...