2-40 HP Portable Chillers
Chapter 7: Appendix
45 of 70
7-3 Drawings and Specifications
2 hp and 3 1/2 hp Air-Cooled Portable Chillers
Nominal operating parameters for air-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton
(9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air. For 50 Hz applications, multiply capacity by 0.83. Nominal 60
Hz capacity flow rate must be maintained
.
Nominal cooling
Water
Com-
Nominal
Power in amps
e
,
HP capacity
c
in tons
flow
pressor
pump
Discharge air
460/3/60
f
no pump
1 pump
gpm
d
hp hp
openings
cfm
g
rated running
2 1.9 1.7 4.6 2.0
1.0
1 @ 18.5”
1,475
8.0
6.9
3.5 3.3 3.1
7.9 3.5 1.0
1 @ 18.5”
2,350
10.9
8.8
c
Based on 50ºF (10ºC) chilled water supply temperature and 95ºF (35ºC) ambient air. Optional additional process
pump hp (kW) reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power).
d
Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump.
e
An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total
chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1
on page 16), and add it to the chiller rated or running amperage.
f
Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages.
g
To convert cfm to cmh, multiply by 1.699.
2 and 3 1/2 hp portable chillers come standard with 2 1/2” (
63 mm
) swivel casters.
Process
Dimensions
Weights
Compressor connections inches
c
Dry
d
Ship.
d
Oper.
d
e
hp in.
NPT
height
width
depth
lbs.
lbs.
lbs.
2.0
¾” or 1.0”
49.7” 22.0” 41.7” 387 417 437
3.5 1.0”
49.7”
22.0” 41.7” 410 440 460
c
To convert to
cm
, multiply by
2.54
. Add to height dimension based on mounting options.
d
Weight is for standard chiller. Some optional features will increase weight. Multiply lbs. by
0.454
to calculate
Kg
.
e
Operating weight is with a full 6-gallon (
22.7 liter
) reservoir tank of water.