SMC Series Chillers
Page 19
3-3 High Pressure Cutout
The high pressure cutout is an electro-mechanical safety feature that opens the control
circuit if the system condensing pressure exceeds a safe level. The chiller will
automatically restart when the pressure drops back to an acceptable level.
Model
Cuts out if condensing pressure exceeds:
SMC050
275 psi (1,897 kPa)
SMC100
275 psi (1,897 kPa)
SMC150
400 psi (2,759 kPa)
IMPORTANT!
Call a refrigeration service technician to analyze
the problem if high pressure recurs.
3-4 Low Pressure Cutout
The low pressure cutout is an electro-mechanical safety feature that prevents
compressor suction pressure from dropping below a preset point.
It is factory set to open the control circuit when pressure drops below a safe level. The
chiller will automatically restart when the suction pressure reaches an acceptable level.
Model
Cuts out if suction pressure falls below:
SMC050
15 psi (103 kPa)
SMC100
15 psi (103 kPa)
SMC150
35 psi (241 kPa)
3-5 Remote Start/Stop Interlock
A contact is provided to allow interlocking of the SMC Series Chiller with process
controls. To use this feature, remove the jumper between Terminals X1 and 1 on
Terminal Block 1. Supply a switch or dry contact interlock connected in series between
these two terminals. See Figure 15 and Figure 16 on pages 34 and 35 for more
information.
Содержание 30F to 65F
Страница 12: ...Page 12 SMC Series Chillers Figure 4 SMC Cast Iron Centrifugal Pump Curve 1 3 hp 0 249 kW ...
Страница 20: ...Page 20 SMC Series Chillers Figure 8 SMC Component Identification ...
Страница 36: ...Page 36 SMC Series Chillers Notes ...
Страница 40: ...Page 40 SMC Series Chillers Notes ...
Страница 41: ...SMC Series Chillers Page 41 Notes ...
Страница 42: ...Page 42 SMC Series Chillers Notes Technical Assistance ...