9.  Connect  the  socket  from  the  power  supply  or 

extension cord to the Emitter pins.  

10.  Complete all power connections. 

11.  Reconnect  power  to  the  air  conditioner.    The 

Emitter should emit a bright blue hue, indicating 
that it is working properly. 

12.  Replace outer cover of air conditioner. 

 

M

AINTENANCE

 

Emitters need to be periodically replaced to maintain 
design output.  The change-out basis depends upon 
the application, number of times switched on/off per 
day, and the hours of operation.  Emitters are to be 
replaced when output falls to 50% of initial output (or 

as specified) by actual radiometer measurements.  A 
Steril-Aire UVC Radiometer Kit may be used for 
such measurements.  If a radiometer is unavailable, 
Emitters should be replaced after 9,000 hours of 
use.

T

ROUBLESHOOTING

 

Symptom 

Possible Causes 

Corrective Action 

Emitter does not light 

Momentary loss of power 

Reset Power Turn off power for 10 Seconds, and then 
turn power on. 

Poor connection 

Check connection to Emitter. Check wiring 
connections. Reset Power. 

Incorrect wiring 

Inspect circuit to wiring diagram. 

Dirty pins 

Clean pins. Reset Power. 

System malfunction 

Check system components, interlock door switches, 
relays, motion detectors, etc. 

Emitter reaching end of life 

Replace with new Emitter. Reset Power. 

Defective Power supply 

Replace Power Supply.  

Low Radiometer Reading 

or Visibly Weak Emitter 

Light 

Dirty Emitter or Radiometer  

Clean Emitter.  Clean Radiometer lens. 

Bad Wiring 

Check wiring to Emitter. 

Emitter reaching end of life 

Replace Emitter. 

Emitter too Cold 

If emitter is at or below 35°F (1°C), Emitter is too cold 
to operate properly.  

Red/Orange Emitter 

Emitter reaching end of life 

Replace Emitter. 

 

R

EPLACEMENT OF 

E

MITTERS

 

 

1.  Turn off power to the kit. 
2.  Carefully  pull  and  slide  out  the  Emitter  from  the 

black shrink wrap. Carefully remove Emitter. DO 
NOT CUT THE BLACK SHRINK WRAP. 

3.  Single  Ended  Emitters  must  be  installed  with 

silicone  grease  applied  to  the  female  lead 
socket.  Without  silicone  grease  moisture  can 
enter the socket and damage the socket, voiding 
the warranty. 

4.  Using  a  new  Emitter  and  grasping  only  the 

ceramic  ends,  align  the  Emitter  pins  with  the 
slots  on  the  inside  of  the  black  shrink  wrap  and 
carefully push the pins into the slots until seated. 
The Emitter is now safely locked into place. 

5.  Once the kit is powered, the Emitter should emit 

a bright blue hue. 

 

 
 
 
 

Содержание Unitary Kit for Small Air Handlers

Страница 1: ...itter and weaken structure If necessary clean Emitter using a Steril Aire cleaning kit isopropyl alcohol and a lint free wipe may be substituted Voltages outside of the range designed for the unit will void the warranty and do permanent damage to the entire unit Emitter contains a small quantity of mercury If an Emitter breaks clean and dispose of with care UVC energy may cause damage to non metal...

Страница 2: ...cable can reach the pins of the Emitter and that its wires can reach the power source mount the power supply 3 50 2 08 1 54 3 88 Ø 14 6 INCH 4 PIN CIRCLINE SOCKET 10 INCH UP TO 24 INCH LAMPS 120V P N 40000121 INSULATED FEMALE 0 25 QUICK DISCONNECT 9 2 9 8 6 1 2 LONG POWER SUPPLY 120 TO 230 V 12 TO 42 LAMPS P N 10000166 1 6 32 LONG POWER IN 4 PIN CIRCLINE SOCKET 8 Based on the mounting option selec...

Страница 3: ... to accommodate component A and secure A with screws Slide Emitter partially through A Slide component B collared end first onto power supply s cord or extension cord and install cord onto Emitter pins see Photo 1 Slide Emitter and component B through A and twist and lock B under A s tabs see Photo 2 o U Bracket Connect the socket from the power supply to the Emitter Snap the Emitter s ceramic end...

Страница 4: ...ins Clean pins Reset Power System malfunction Check system components interlock door switches relays motion detectors etc Emitter reaching end of life Replace with new Emitter Reset Power Defective Power supply Replace Power Supply Low Radiometer Reading or Visibly Weak Emitter Light Dirty Emitter or Radiometer Clean Emitter Clean Radiometer lens Bad Wiring Check wiring to Emitter Emitter reaching...

Страница 5: ...Unitary Kit 22000100 RGTS 24 HO 24 Replacement Emitter for Unitary Kit 22000200 EMITTERS for Air Handler Kits GTS 12 VO 12 Replacement Emitter for Air Handler Kit 21000700 GTS 16 VO 16 Replacement Emitter for Air Handler Kit 21000100 GTS 20 VO 20 Replacement Emitter for Air Handler Kit 21000200 GTS 24 VO 24 Replacement Emitter for Air Handler Kit 21000300 GTS 30 VO 30 Replacement Emitter for Air H...

Отзывы: