4
9. Connect the socket from the power supply or
extension cord to the Emitter pins.
10. Complete all power connections.
11. Reconnect power to the air conditioner. The
Emitter should emit a bright blue hue, indicating
that it is working properly.
12. Replace outer cover of air conditioner.
M
AINTENANCE
Emitters need to be periodically replaced to maintain
design output. The change-out basis depends upon
the application, number of times switched on/off per
day, and the hours of operation. Emitters are to be
replaced when output falls to 50% of initial output (or
as specified) by actual radiometer measurements. A
Steril-Aire UVC Radiometer Kit may be used for
such measurements. If a radiometer is unavailable,
Emitters should be replaced after 9,000 hours of
use.
T
ROUBLESHOOTING
Symptom
Possible Causes
Corrective Action
Emitter does not light
Momentary loss of power
Reset Power Turn off power for 10 Seconds, and then
turn power on.
Poor connection
Check connection to Emitter. Check wiring
connections. Reset Power.
Incorrect wiring
Inspect circuit to wiring diagram.
Dirty pins
Clean pins. Reset Power.
System malfunction
Check system components, interlock door switches,
relays, motion detectors, etc.
Emitter reaching end of life
Replace with new Emitter. Reset Power.
Defective Power supply
Replace Power Supply.
Low Radiometer Reading
or Visibly Weak Emitter
Light
Dirty Emitter or Radiometer
Clean Emitter. Clean Radiometer lens.
Bad Wiring
Check wiring to Emitter.
Emitter reaching end of life
Replace Emitter.
Emitter too Cold
If emitter is at or below 35°F (1°C), Emitter is too cold
to operate properly.
Red/Orange Emitter
Emitter reaching end of life
Replace Emitter.
R
EPLACEMENT OF
E
MITTERS
1. Turn off power to the kit.
2. Carefully pull and slide out the Emitter from the
black shrink wrap. Carefully remove Emitter. DO
NOT CUT THE BLACK SHRINK WRAP.
3. Single Ended Emitters must be installed with
silicone grease applied to the female lead
socket. Without silicone grease moisture can
enter the socket and damage the socket, voiding
the warranty.
4. Using a new Emitter and grasping only the
ceramic ends, align the Emitter pins with the
slots on the inside of the black shrink wrap and
carefully push the pins into the slots until seated.
The Emitter is now safely locked into place.
5. Once the kit is powered, the Emitter should emit
a bright blue hue.