2
the possible hazard of looking at or exposing
skin to UVC energy. Service accesses may be
equipped with a glass or Lexan
®
window
(viewport) to view Emitters. UVC energy does
not penetrate common glass or Lexan
®
.
3. If applicable, remove outer cover of unitary air
conditioner or air handler.
4.
UVC energy may damage some plastics except
HVAC-style drain pans. Wrap suspect items with
aluminum tape; use metallic conduit or use other
appropriate shielding where these items may be
in "line of sight" of the UVC energy.
6.
Determine location of the Emitter.
(Many types
of unitary air conditioners have a removable
shroud/heating
coil
assembly
that
may
adequately accommodate the Emitter.)
The
Emitter shall:
o
Be at least 1” away from the heating coil.
o
Not make contact with the blower.
o
Provide direct light onto the cooling coil and
drain pan.
o
Be positioned so there is no direct, visible
light from outside of the unitary air
conditioner. A baffle may be installed to
provide any needed light blockage.
CAUTION: Do not drill into coil, refrigerant lines
or other mechanical equipment.
7. Determine an appropriate flat-surfaced location
for mounting the power supply with the provided
screw
s. Make sure that the power supply’s lead
socket (with extension cord, if applicable) can
reach the pins of the Emitter and that its wires
can reach the power source; mount the power
supply.
3.50
2.08
1.54
3.88
Ø .14
6 INCH
4 PIN
CIRCLINE
SOCKET
10 INCH
UP TO 24 INCH LAMPS
120V P/N 40000121
INSULATED FEMALE
0.25" QUICK-DISCONNECT
9.2
9.8
6-1/2" LONG
POWER SUPPLY 120 TO 230 V
12 TO 42" LAMPS P/N 10000166
1.6
32" LONG
POW ER IN
4 PIN CIRCLINE
SOCKET
8. Based on the mounting option selected, use the
following instructions for installation. Install the
Mounting Bracket(s) and Emitter.
o
Spring Clips:
Mount clips on existing panel
facing the coil. The clips should be attached to
the Emitter on both ceramic ends. If the spring
clips must contact the Emitter glass, 3 wraps of
electrical tape are recommended at the points
of contact to prevent the spring clips from
damaging the Emitter wires along the lamp. If
the wires running the length of the lamp have
been damaged, the warranty is void.
Short Hooks
: Remove spine/top plate between
the two upper coils. Cut spine/top plate in order
to accommodate the support wire. Insert the
short hooks over the top of the cooling coils
such that its right angle leg slides between the
fins of the front coil (see below). Ensure that
Emitter ceramic ends rest on the Short Hooks
(see below).
Reinstall the spine/top plate pieces. In some
cases, one Short Hook may be sufficient where
1.25"
2.4"
.98
Ø .18
.60
or 230 V P/N 40000124
6 in. for 120 V, 14 in. for 230 V
Unitary Kit Power
Supply
Air Handler Kit