Issue 4
6
Control push buttons
Icon
Description
Stop / Reset Mode
This button places the module into its
Stop/Reset Mode
. This clears any alarm conditions
for which the triggering criteria have been removed. If the engine is running and the module is
put into Stop mode, the module automatically instructsthe generator to unload (
Close
Generator and Delayed Load Output 1, 2, 3 & 4become inactive (if used))
. The fuel supply
de-energises and the engine comes to a standstill. Should any form of
remote start signal
be
present when in
Stop Mode
the generator remains at rest
Manual Mode
This button places the module into its
Manual Mode
. Once in
Manual Mode
, the
module responds to the
Start
button to start the generator and run it off load.
Auto Mode
This button places the module into its
Auto Mode
. This mode allows the module to control
the function of the generator automatically. The module monitors the
remote start
input and
once a start request is made, the set is automatically started and placed on load
Upon removal of the starting signal, the module removes the load from the generator and
shut the set down observing the
stop delay
timer and
cooling
timer as necessary. The module
then waits for the next start event.
Alarm Mute / Lamp Test
This button de-activates the audible alarm output (if configured) and illuminates all of the
LEDs on the module’s facia.
Start
This button is only active in the
Stop/Reset Mode
and
Manual Mode
.
Pressing the
Start
button in
Manual Mode
starts the generator and runs it on load.