![Stephill SSDP30 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/stephill/ssdp30/ssdp30_handbook_1372631012.webp)
Issue 4
10
When the event log is full, any subsequent event overwrites the oldest entry. Hence, the event log always
contains the most recent events. The module logs the event type, along with the date and time (or engine
running hours if configured to do so).
To view the event log, press and hold either of the
Menu Navigation
buttons to scroll to the Event
Log page.
Press the
Scroll Down
button to view the next most recent event.
Continuing to press the
Scroll Down
button cycles through the past events after which, the
display shows the most recent alarm and the cycle begins again.
To exit the event log and return to viewing the instruments, press and hold either of the
Menu Navigation
buttons to select the next instrumentation page.
7 OPERATION
7.1 STARTING THE ENGINE
Manual Start
Press the
Manual Mode
button.
Press the
Start
button.
7.2 STOPPING THE ENGINE
Press Stop/Reset
mode. The generator is stopped.
7.3 STOP/RESET MODE
Stop/Reset Mode
is activated by pressing the
Stop/Reset Mode
button.
In
Stop/Reset Mode
, the module removes the generator from load (if necessary) before stopping
the engine if it is already running.
If the engine does not stop when requested, the
Fail To Stop
alarm is activated (subject to the setting
of the
Fail to Stop
timer). To detect the engine at rest the following must occur :
Engine speed is zero.
Generator AC Voltage and Frequency must be zero.
Engine Charge Alternator Voltage must be zero.
Oil pressure sensor must indicate low oil pressure.
When the engine has stopped, it is possible to send configuration files to the module from DSE
Configuration Suite PC software and to enter the Front Panel Editor to change parameters.
Any latched alarms that have been cleared are reset when
Stop/Reset
Mode
is entered.
The engine is not started when in
Stop/Reset Mode
. If remote start signals are given, the input is
ignored until
Auto Mode
is entered.
When left in
Stop/Reset Mode
with no presses of the fascia buttons and configured for
Power
Save Mode,
the module enters
Power Save Mode
. To ‘wake’ the module, press any fascia control
buttons.