Example: 

 

 

 

In the event of an alarm the LCD jumps to the alarms page, and scroll through all active alarms. 
 
By default, warning alarms are self-resetting when the fault condition is removed. 
 
Fault 

Description 

Analogue Input A to D 
 

The module detects that an input configured to create a fault condition has 
become active and the appropriate LCD message is displayed. 

Battery Over Voltage 

The DC supply has risen above the 

high volts pre-set 

pre-alarm setting. 

Battery Under Voltage 
 

The DC supply has fallen below or risen above the 

low volts preset 

pre-

alarm setting. 

Charge Alternator Failure 
 

The auxiliary charge alternator voltage is low as measured from the W/L 
terminal. 

Coolant Temperature Sensor 
Fault 

The module detects that the circuit to the coolant temperature sensor has 
been broken. 

Delayed Over Current 
 

The measured current has risen above the configured trip level for a 
configured duration. 

Digital Inputs A to F 
 

The module detects that a digital input which has been user configured to 
create a fault condition has become active and the appropriate LCD 
message is displayed. 

Expansion Unit Failure 

The module detects the DSE Net link to the expansion module has failed or 
communications to the expansion module has been lost. 

Fail To Stop 
 

 

The module has detected a condition that indicates that the engine is  
running when it has been instructed to stop. 

Low Fuel Level 
 

The level detected by the fuel level sensor is below the 

low fuel level pre-set 

pre-alarm setting. 

Maintenance Alarm 1 
 

The module detects that the Maintenance Alarm 1 is due creating a fault 
condition, the appropriate LCD message is displayed. 

Maintenance Alarm 2 
 

The module detects that the Maintenance Alarm 2 is due creating a fault 
condition, the appropriate LCD message is displayed. 

Maintenance Alarm 3 
 

The module detects that the Maintenance Alarm 3 is due creating a fault 
condition, the appropriate LCD message is displayed. 

Oil Pressure Sensor Fault 

The module detects that the circuit to the oil pressure sensor has been 
broken. 

 

8.3 ELECTRICAL TRIP ALARMS

 

 

 
Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip 
condition the module de-energises all the 

Delayed Load Output 

and the 

Close Gen Output 

outputs to remove 

the load from the generator. Once this has occurred the module starts the Cooling timer and allows the 
engine to cool off-load before shutting down the engine. The alarm must be accepted and cleared, and the 
fault removed to reset the module. 
 

 

Содержание SSDP30

Страница 1: ...stephill generators co uk Web Web www stephill generators co uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS ST...

Страница 2: ...PERATION 10 7 1 Starting the engine 10 7 2 Stopping the engine 10 7 3 Stop Reset mode 10 11 7 4 Manual mode 11 7 4 1 Starting sequence 11 7 4 2 Stopping sequence 11 7 5 Automatic mode 11 7 5 1 Waiting...

Страница 3: ...run are based on these figures 2 GENERAL SAFETY 2 1 Warning signs Warnings shown on the machine should be observed at all times The warning signs should be checked for legibility and any that have be...

Страница 4: ...orms of contact are irritant and therefore should also be avoided If skin contact is made wash with soap and water 4 3 Bunded tank This generator is fitted with a secondary containment system Bunded t...

Страница 5: ...generator unless all guards are in place There is a risk of burns or serious mechanical injury 5 OPERATING INSTRUCTIONS 5 1 Pre start checks Before starting the generator please read the engine owners...

Страница 6: ...e possibility of an automatic or manual reset selectable by a microswitch and to protect the settings by its sealable transparent front cover 1 Current tripping setting potentiometer 2 Tripping time s...

Страница 7: ...es and hoses should be checked to ensure that they are un perished following extended periods of storage The generator should be stored in a clean dry area ideally having a reasonable constant ambient...

Страница 8: ...e responds to the Start button to start the generator and run it off load Auto Mode This button places the module into its Auto Mode This mode allows the module to control the function of the generato...

Страница 9: ...strumentation page the instruments displayed are automatically subject to the setting of the LCD Scroll Timer The screenshot below shows the factory settings for the timers taken from the DSE Configur...

Страница 10: ...Alarm on the module Press and hold either of the Menu Navigation buttons to scroll to the alarms page to investigate Press the Stop Reset Mode button to clear the alarm if the alarm does not clear the...

Страница 11: ...the Alarm Page The LCD displays multiple alarms such as Coolant Temperature High Emergency Stop and Low Coolant Warning These automatically scroll in the order that they occurred In the event of an a...

Страница 12: ...Reset Mode is activated by pressing the Stop Reset Mode button In Stop Reset Mode the module removes the generator from load if necessary before stopping the engine if it is already running If the en...

Страница 13: ...either The Stop Reset Mode button is pressed The delayed load outputs are de activated immediately and the set immediately stops The Auto Mode button is pressed The set observes all Auto Mode start re...

Страница 14: ...The Cooling Down timer allows the set to run off load and cool sufficiently before being stopped This is particularly important where turbo chargers are fitted to the engine After the Cooling Down tim...

Страница 15: ...the expansion module has failed or communications to the expansion module has been lost Fail To Stop The module has detected a condition that indicates that the engine is running when it has been ins...

Страница 16: ...load from the generator Once this has occurred the module shuts the generator set down immediately to prevent further damage The alarm must be accepted and cleared and the fault removed to reset the m...

Страница 17: ...below the under speed trip alarm setting 8 5 HIGH CURRENT SHUTDOWN The overcurrent alarm combines a simple warning trip level with a fully functioning IDMT curve for thermal protection Alarm is set at...

Страница 18: ...ervice engineer after performing the required maintenance The method of reset is by breaking the connection between wires 43 1 which are located at the side of the MCCB Panel must be powered up for re...

Страница 19: ...ilable and within configured limits Generator fails to start on receipt of Remote Start signal Check Start Delay timer has timed out Check signal is on Remote Start input Confirm correct configuration...

Страница 20: ...n the DC connector plug and socket Check continuity on VE and VE wires to battery Battery not Note you may experience low charge if fan belt is loose charging Check for loose wires on the DC connector...

Страница 21: ...59 018 0059 018 0059 Reactive silencer MK1 1 st Silencer 016 0133 016 0133 016 0175 016 0175 016 0175 Absorption Silencer MK1 With tail pipe 016 0135 016 0135 016 0176 016 0176 016 0176 U Pipe with ab...

Страница 22: ...nning Ensure battery isolator switch is in the off position when working on generator this will prevent generator from starting 13 1 Engine service Service the engine strictly in accordance with the i...

Страница 23: ...use of parts not supplied by STEPHILL GENERATORS LTD Lack of or incorrect maintenance Fair wear and tear misuse negligence accidental damage improper storage incorrect starting warm up run in or shut...

Страница 24: ...wn 4mm Black 4mm Grey 6mm Grey 6mm Brown 6mm Black 6mm Grey 6mm Black 6mm Brown 6mm Blue 6mm Green Yellow Hard wire terminals 50A MCB W 27 V 26 U 25 N 28 1 5mm Grey 1 5mm Black 1 5mm Brown 37 34 33 37...

Страница 25: ...L1 N E L2 L3 32A MCB 4mm Blue 1 5mm Blue 4mm Brown 4mm Black 1 5mm Grey 4mm Grey 4mm Black 4mm Brown 10mm Grey 10mm Blue 10mm Black 10mm Brown 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 4 3 2 1 28...

Страница 26: ...53 38 REMOTE START VE 1 BATTERY VE 2 5mm 1 COOLANT SWITCH 51 1 41 9 41 1 41 B D C 2 BATTERY VE CLOSE TO START REMOTE START VE 1 HARD WIRE DOOR 42 1 VE 2 FUEL A 4 START B 5 EMERGENCY STOP 3 C 7 D 8 CHA...

Страница 27: ...3 10 11 27 6 25 22 21 30 17 7 39 40 42 36 41 5 43 14 15 R Golding A 30 06 14 New drawing Date Revision Issue THIRD ANGLE PROJECTION Description Fax Phone Drawing Number Drawn SSDP33 70 Mk2 Exploded vi...

Страница 28: ...SSD30 Silencer bracket 21 016 0121 SSD30 Silencer bracket 22 016 0272 SSD30 MK2 Air outlet deflector plate 22 016 0272 SSD30 MK2 Air outlet deflector plate 23 016 0119 SSD30 Radiator plate 23 016 0119...

Отзывы: