21
USA and Canada 800.683.2378, International 904.641.1666
Econ FP
MODE
%
1.
Connect signal wires as required by the installation:
SECONDS
Black & Red
FLOW SWITCH
Black & Red
PAUSE
Green & White
AUXILIARY
Brown (or Orange) & Blue
- For AC signal, there is no polarity.
- For DC signal, blue wire is connected to signal positive (+) and brown (or orange)
is connected to signal negative (—).
NOTE: If polarity is reversed when connecting a DC signal to the AUX input, the
pump will not respond to the signal.
2.
Cap all non-terminated wires.
NOTE: All non-terminated wires must be capped to prevent operational errors or damage to
the pump.
3.
Plug power supply into receptacle. To unlock the keypad, simultaneously press and
hold and for 5 seconds.
4.
Put the pump in standby. First, press and continue to hold
, then press
.
5.
Program the pump for the desired operating mode and
%
setting, refer to Program
Pump Settings in the manual.
NOTE: Leave the unit in standby until the signal wires are connected and the pump is
ready for priming.
INSTALLATION
SECONDS
or
FLOW SWITCH
PAUSE
Brown
(or Orange)
Blue
Green
Black
Red
White
AUXILIARY
STBY
MODE
+
—