The master/slave configuration
permits detection of movement in
large-type rooms or spaces (load
connected = master, no load =
slave). The level of brightness pre-
vailing in the room is only evaluat-
ed at the master. The slaves report
movements detected to the mas-
ter. Lighting or HVAC is switched
'ON' and 'OFF' by the master only.
Master/slave
A parallel-connected configuration
also permits the use of several
masters. In this case, each master
operates the lighting group in
accordance with the level of
brightness it measures. Delay
times and brightness thresholds
are selected at each master as re-
quired. The switched load is spread
among the individual masters.
Presence is still detected collec-
tively by all detectors. The pres-
ence output can be picked off
from any master.
Master/master
Remote control
Using the remote control (option-
al), functions can be conveniently
activated from the floor.
Note: The pulse mode cannot be
overridden by the remote control.
Switch pulse mode 'OFF' manually.
Presence Control remote control
unit: EAN no.: 4007841 000387
Parallel-connected configurations
Two detectors linked with an
external stairwell lighting
timer
Old building / building moderni-
sation
External light source activated by
button. No twilight mode, day
mode only.
Detector as stairwell lighting
timer
14.
1
14.
2
14.
3
14.
4
When using several detectors, they must be connected to the same phase!
DIM
detector
14.
5
• Setting 1 sec. – 2 hr.
• Turned fully clockwise: max
• Turned fully anti-clockwise: min
• Setting 0 sec. – 10 min.
• Turned fully clockwise:
Room surveillance
• Turned fully anti-clockwise:
0 sec. ('OFF')
Turning the potentiometer to the
"Surveillance" setting reduces the
sensitivity of the "Presence"
switching output. The contact only
closes on detecting a pronounced
movement, signalising with a high
degree of certainty that persons
are present.
The stay-'ON- time remains
active. The switch-'ON' delay
is inactivated.
Switch-'ON' delay for switching output 2 HVAC
Reach adjustment
COM 2
Potentiometer
Potentiometer
Provides basic illumination for the
selected stay-'ON' time when ambi-
ent light falls below the selected
brightness threshold that is set. This
can be dimmed to 10% of maxi-
mum light intensity. As soon as a
person enters the scene, the detec-
tor switches either to 100% light
intensity (constant-lighting control-
ler 'OFF') or adjusts to the preselect-
ed brightness level (constant-light-
ing controller 'ON'). When no move-
ment is being detected, the detec-
tor dims back to basic brightness
after the stay-'ON' time expires. This
is switched 'OFF' when stay-'ON'
time (1 min. – 30 min.) has expired
or the daylight component is suffi-
cient to exceed the selected level of
brightness. In the 'ON' setting, the
detector switches basic brightness
'ON' and 'OFF' as soon as the level
of light falls below the brightness
threshold.
Basic brightness (DIM option)
Potentiometer
Stay-'ON' time for switching output 2 HVAC
The reach required (response
threshold) is infinitely variable.
HF 360
1 m min. – 8 m max.
DUAL HF
min. 3 x 3 m – 10 x 3 m in
each direction
Turned fully anticlockwise
(factory setting) = minimum reach
Turned fully clockwise
(factory setting) = maximum reach
Potentiometer