Technical Specifications
Electrical installation/Automatic mode
In selecting the wiring leads, it is
important to meet the wiring
regulations laid down in VDE 0100
(see Safety warnings on page 19).
The following applies to wiring
presence detectors: According to
section 6 of VDE 0100 520, a multi-
ple-core lead containing both the
mains voltage leads and the con-
trol leads (e.g. NYM 5 x 1.52) may
be used for wiring between the
sensor and electronic ballast. The
mains connection lead must be no
greater than 10 mm in diameter.
The clamping range of the mains
terminal is designed for a maxi-
mum of 2 x 1.5 mm
2
or 1 x 2.5 mm
2
.
P S N
L L'
L
N
P
L
N
COM1
P S N
L L'
L
N
L
N
1-10V
1-10V
+ –
max. 100 mA
DIM
DIM
COM 1
COM 2
COM 1 AP
GB
Dimensions
(w x h x d)
HF 360
120 x 120 x 56 mm
Dual HF
120 x 120 x 76 mm
Supply voltage
230 – 240 V, 50 Hz / 60 Hz
Capacity,
switching output 1
(COM 1/COM 2)
Relay 230 V
Resistive load 2000 W max. (cos
ϕ
= 1)
1000 VA max. (cos
ϕ
= 0,5)
Electronic ballast:
(COM 1/COM 1 AP/
COM 2/DIM)
Max. 'ON' current 800 A/200 μs
30 x (1 x 18 W), 25 x (2 x 18 W)
25 x (1 x 36 W), 15 x (2 x 36 W)
20 x (1 x 58 W), 10 x (2 x 58 W)
Pay attention to specific 'ON' currents of electronic ballasts!
A relay or contactor must be provided on line side for higher switching
capacities.
Capacity,
switching output 2
(COM 2 only) (HF 360 only)
Presence
230 W max. / 230 V
1A max. (cos
ϕ
= 1) for HVAC (heating/ventilation/air-conditioning)
Application
indoors
Mounting height
(mounted to ceiling)
2.5 m – 3.5 m ceiling height
Detection angle
HF 360
360° with 140° aperture angle
also through glass, wood and
stud walls. 1 or 2 detection direc-
tions can be masked out for ad-
justment to the room situation.
Dual HF
see diagrams on p. 21
also through glass, wood and stud
walls
Reach
HF 360
8 m max. all round,
electronically and infinitely
variable
Dual HF
10 x 3 m max. in each direction,
electronically and infinitely
adjustable
Switching output 1
Time setting
30 sec. – 30 min., pulse mode (approx. 2 sec.)
IQ mode (automatic adjustment to use profile)
Switching output 2
Time setting
(HF 360 only)
COM2 only for HVAC
0 sec. – 10 min. switch-'ON' delay
1 min. – 2 h stay-'ON' time
Automatic room surveillance
DIM:
Time setting
30 sec. - 30 min.
IQ mode (automatic adjustment to use profile)
Control output
1 – 10 V / max. of 50 electronic ballasts, max. of 100 mA
Sensor system
High-frequency 5.8 GHz, transmission power < 1mW
Function setting by
DIP switches
DIP 1 Normal / test mode
DIP 2 Semi- / fully automatic mode
DIP 3 Button / switch mode
DIP 4 'ON' button / 'ON'-'OFF' button
DIP 5 Constant-lighting control 'ON'-'OFF' (DIM)
Parallel connections
Master/slave
Master/master
User-friendly setting capability Teach-in (with optional remote control RC3)
Light-level setting
10 – 1000 lux, ∞ / daylight
DIM 100 – 1000 lux
IP rating
IP 20 (IP 54 with surface-mounted box)
Safety class
II
Temperature range
0° to +40° C
Housing
UV-resistant, paintable