a
ppendix
| a.02
T
herm
e
lecT
h
ydronic
Model 9180 (80kW Storage Module)
Input Voltage
277/480
347/600
Phase
3
3
Number of Wires
4
4
Charging Input (kW)
75.6
80
Elements - Quantity
Elements - Watts Each
18
4,200
18
4,444
Amps - Core Charging
90.97
76.84
Max. Pump & Blower Load (AMPS)
2.3
1.9
Minimum Circuit Ampacity
116.59
98.43
Minimum Fuse Size
125
100
Maximum Fuse Size
150
125
Blower/System Control Voltage
*
240V/208V
Storage Capacity - kWh
**
Storage Capacity - BTU
440
1,501,280
Pipe Size (Inlet/Outlet)
1 1/2”
Required Primary Loop
***
Minimum of 12’ of 1.25” pipe in primary loop plumbing
Output Water Temperature (selection range)
50
o
F to 185
o
F
Maximum Working Pressure
20 PSIG requires 30 PSI Pressure Relief Valve
60 PSIG requires 75 PSI Pressure Relief Valve (Standard)
125 PSIG requires 150 PSI Pressure Relief Valve
Minimum Flow Rate (Primary Loop)
1 GPM per 10,000 BTU of required output at 20
o
F
Temperature Rise (30 GMP Maximum)
Internal Pressure Drop
(assuming 50% glycol mix)
.7 ft @ 15 GPM 1.8 ft @ 25 GPM
1.2 ft @ 20 GPM 2.5 ft @ 30 GPM
Maximum Static Dissipation (Watts)
4,500
Appropriate Heater Module Weight (lbs)
1,166
Approximate Insulation Block/Elements/Other Weight
(lbs)
372
Approximate Brick Weights (lbs)
4,767
Number of Bricks
288
Approximate Installed Weight (lbs)
****
6,305
*
Supply via stepdown transformer - field installed.
**
Storage capacity is based on maximum core temperature of 1400 degrees Fahrenheit.
***
Heat exchanger inlet and outlet are 1.5” diameter. Reducers will be required using 1.25” pipe for primary loop.
****
Approximate total shipping weight (lbs) 7,030 lbs.